Integration of Building Systems Flashcards
What are 3 things to know for calculating the size of an HVAC system?
- The capacity of heating/cooling equipment that the building needs (aka total heat gains/losses in most extreme conditions)
- The size of spaces required to house mechanical equipment
- The space and layout needed for pipe/duct distribution
What are 5 variables that influence the amount of space required for an HVAC system?
- scope of the system (local, centralized, or district)
- type of the system (air, water, air-water, electric)
- building size.
- building type
- any passive systems used
What is the difference between local, centralized, or district HVAC systems? How much space does each need relative to the others?
Local: serves one zone, used for small buildings or specific area of a large building
Needs the least space
Centralized: serves several zones from one location. Common in moderate to large buildings, often commercial and institutional.
Needs the most space
District: serves several buildings from a single plant. Common in a campus.
Needs less space than centralized because heating/cooling takes place elsewhere.
How much space does each type of system need:
- relate to the others?
- as a % of building size?
- all air
- all water
- air-water
- electric
- direct expansion
- All air: needs the most space (3%-10% of total building area)
- Air-water: needs medium amount of space because no return air ducts are needed, just supply ducts (3%-10% of total building area)\
- All water: needs least amount of space (1%-3% total building area)
- Electric: smallest and simplest. Limited to small buildings with localized system. (<1% total building area)
- Direct expansion: smallest and simplest. Limited to small buildings with localized system. (<1% total building area)
Where should a cooling tower be located?
Locate on roof or outside
Where should a boiler be located?
How much clear height does a boiler need?
How many boilers does a building typically have?
How much floor area sf does a boiler chimney require?
Where should a chiller be located?
Boilers must be placed inside, in a room about twice the boiler’s length
- Clear height of 12’-8” is required
- Typically 2 boilers
- Boiler chimneys need about 4sf - 36 sf floor area
Chillers are often are in same room as boilers, may be in separate room
AHU
- what does it do?
- when do you need one?
- what kind of ductwork is required?
- where should it be located
- what the equipment is included in the same room?
Air Handling Unit
- Uses water from boilers and chillers to heat or cool the air
- Need if you have an all-air or all-water system
- Requires supply ductwork to run from the AHU to each terminal unit and supply air diffuser
- should be located in the fan room, next to an exterior wall (can be more interiorly located if fresh air and exhaust can be carried by ductwork)
- fan room should also contain fans, filters, humidifiers, preheat coils (cold climates), return air ducts, outside air intakes, exhaust points, dampers, mixing box
What equipment is included in the fan room?
Where should the fan room be located?
Any other fan room considerations?
- AHU, fans, filters, humidifiers, preheat coils (cold climates), return air ducts, outside air intakes, exhaust points, dampers, mixing box
- Next to an exterior wall (can be more interiorly located if fresh air and exhaust can be carried by ductwork)
- Equipment is very noisy
- Locate so as to minimize ductwork
Where are 3 options for location a mechanical room and fan room in a large or high-rise building? Which option provides the greatest smoke control?
- In the basement along with a primary fan room that distributes air upward
- In the basement with smaller fan rooms located on each floor
* * This option provides greater smoke control in case of fire = air supply to a particular floor can be switched off, and return air exhausted to outside while dampers on floors above/below can be switched on to provide full pressurization to prevent spread of smoke** - Roof or mechanical penthouse – must consider noise control and structural support
What is a difference between round and rectangular ducts?
Round = more efficient and maintains air pressure better Rectangular = makes better use of space above ceilings and in vertical chases
Where should horizontal trunk ducts be located?
Along paths of building circulation systems
Above corridor ceilings or between/under structural beams
What is static head (or static pressure) in air ducts?
The amount of pressure that must be applied to overcome the resistance/friction between moving air and duct walls
What is a rule of thumb for static head/pressure in relation to…
- duct length?
- duct size/diameter?
- fan size?
Summarize all this into one statement.
- The longer the ductwork, the more friction in the system and larger ducts or larger fans are required to overcome it
- Increasing the size of ducts keeps pressure lower, but requires more space
- Increasing the size of fans raises pressure, but raises initial & operation costs and creates more noise
SO if you can keep the duct runs shorter, you can use a higher pressure system (which will take up less space) and smaller fans (which keep costs lower and reduce noise)
What is a mixing box?
How is it controlled?
How big is it?
Where is it located?
Controls air that flows into a space from the main air supply line.
By a thermostat – it adjusts the air’s quantity and/or temperature while reducing air’s velocity and noise
Depends on type and capacity of system. Can range from 6in–18in tall, 24in–60in long, 14in–66in wide
In the plenum
How does a mixing box work in a terminal reheat system? What is one way to identify a terminal reheat system?
Cool air enters mixing box at a fixed temperature, and the mixing box contains a hot water coil that can add heat as needed
You can identify a terminal reheat system by the air ducts and copper pipes leading into the mixing boxes
How does a mixing box work in a dual duct system?
The mixing box receives both cool air and hot air from two separate ducts, and mixes them to obtain the needed temperature. Then it distributes the mixed air.
How does a mixing box work in a VAV system? Where is it typically located?
The VAV mixing box receives air at a constant temperature and then varies the airflow rate as needed to maintain desired temperature.
VAV box is typ placed above the ceiling within or near the space it serves
What is a plenum?
What is it used for? How much space does each use need?
The space between a suspended ceiling and the structural floor or roof
Used for:
1. Mech = Ductwork = 12in – 16in depth
- Plumbing = Sprinkler & plumbing piping = 4in – 6 in of depth
- Electrical = Wiring, signal systems, speakers, and recessed lighting =
9in–12in (compact fluorescent downlights)
4in–5in (standard fluorescent fixtures)
<4in (LED and improved compact fluorescent)
Suspended ceiling = 2in
total space need = 22” - 42”
What is access flooring?
an alternative to a plenum in which a false floor of individual panels is raised above the structural floor by pedestals. Most commonly used for communication, electrical, and computer wiring but can be used for HVAC.
Where should supply diffusers be located?
Where should return air diffusers be located?
Supply diffusers = near windows
Return diffusers = Away from supply points (for circulation)
What is static head in water supply? Water pressure?
Static head = pressure is expressed in linear feet (think: a column of water)
Water pressure = pressure expressed in psi
Identify the static head and water pressure in this statement:
“A column of water 1ft tall exerts a pressure of 0.433 psi at its base”
Static head = 1ft
Water pressure = 0.433 psi
Identify the static head and water pressure in this statement:
“1 psi of pressure will raise water 2.3 ft”
Static head = 2.3 ft
Water pressure = 1 psi
What are the 2 primary types of water supply systems?
What is the difference?
When should each be used?
upfeed & downfeed
upfeed = uses pressure in the water main to directly supply the fixtures
- Height limit = 40ft–60ft
downfeed = water from main is pumped to storage tanks near the top of the building and flows to the fixtures by gravity
- Use if building is too tall for upfeed
- Height limit = ~138ft
Where is water pressure lowest in a downfeed system? Where is it highest?
Pressure is lower at the top = highest fixture has a min pressure
Pressure is highest at the bottom = bottom fixture has a max pressure
What is a direct upfeed pumping system or tankless system?
Where can it be used?
Several pumps are used together and controlled by a pressure sensor
- When demand is light, only one pump operates
- When demand increases, another pump is signalled to start
Use for medium-sized buildings
what are 4 grades of copper and what are they used for?
K = thickest walls
Available in straight lengths (hard temper) or coils (soft temper)
L = thinner walls = most commonly used for building plumbing systems
Available in straight lengths or coils
M = thinnest walls = used only where low pressure (branch supply lines, chilled water systems, exposed lines in heating systems, and drainage piping)
Available in straight lengths or coils
DWV = thinner than L, rarely used now
When can you use Steel or galvanized steel piping?
use where water is noncorrosive
Schedule-40 pipe most often used
When can you use plastic piping? What 2 main types are used in plumbing?
check code - plastic is restricted by building type and plastic type
CPVC (chlorinated polyvinyl chloride)
PEX (cross-linked polyethylene)
** Note: PVC is only used for cold water supply and drainage
What are valves used for in plumbing? Where are they located?
Used to control water flow. Allow selective shutdown of the system for repairs without affecting the entire building.
Risers, horizontal branch lines, and pipe connections to fixtures/equipment
What is the use for a ball valve?
ball valve = used as main shutoff valve
What is the use for an angle valve?
angle valve = used to control water supply to an individual fixture, for maintenance work
What is the use for a pressure reducing valve?
pressure reducing valves = used when the supply pressure from the street is greater than the building’s needs