According to industry standards, all distribution transformers above 200 kVA and/or 8,600 volts are ?
subtractive
In order for a single-phase transformer to produce any secondary voltage, the X2 grounding strap must be in place.
false
A CSP transformer contains a(n) ? and a ? breaker.
internal hv fuse / secondary
If a transformer nameplate shows 14,400/24,940 Y, it is suitable for a delta connection because it has full insulation ?
at the h2
A transformer with reduced insulation at H2 must have H2 tied to the ?
systems neutral
If the secondary voltage is listed on a transformer as 120/240 or 240/120, it makes no difference, as both internal secondary coils can be connected in parallel or series.
false
Aluminum triplex itself can be inserted in the transformer lugs.
false
A popsicle stick connector is a(n) ? terminal connector that is squeezed onto the end of the wire and inserted into the secondary terminals of a transformer.
pin
On a fully loaded 25 kVA transformer, the drop leads would normally be ? stranded copper.
2
One factor that affects the mass that may be attached to a pole is the ?
class of pole
While conducting a pre-installation check on a transformer, do not ? unless permission is granted by the employer.
remove the lid
On a transformer with basket terminals, copper leads should be inserted from the ?
top
If more than one popsicle stick connector is to be installed in a basket type transformer terminal, ? leads should be brought out to connect the services.
copper
If a transformer was ordered 24,940 Grd Y/14,400, the transformer would have ? insulation at the H2 end.
reduced