What is a level control switch?

A

Magnetically actuated for close control of liquid level and maintains close control of liquid level. It is a metering device and can be used as a high side float.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What 2 types of compressors are used in industrial refrigeration?

A

screw and semi-hermitic

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the benefit of screw compressors?

A

Require less maintenance and are efficient

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the primary side of the ice rink?

A

The side that has the evaporative condenser and compressor which has the refrigerant in it.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the secondary side of the ice rink?

A

The ice sheet and evaporator which has the brine in it.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the 2 types of flooded evaporators used?

A

shell and tube and plate exchanger

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

In the flooded evaporator where is the primary (R-717) and secondary refrigerant (brine)?

A

In the shell and the brine is in the tubes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What does a surge drum do?

A

Prevents liquid from getting back to the compressor and is located on top of the flooded evaporator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the advantage of the plate heat exchanger?

A

It is smaller and less maintenance

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Where is the high side float located and what does it do?

A

It is located between the condenser and evaporator. It responds to the load on the condenser. As the load increases it allows more liquid through the float valve into the condenser.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where is the low side float located and how does it operate?

A

In the chiller or next to the chiller in a column of liquid. When liquid refrigerant level is low the valve allows liquid in to increase flow.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is a high side float pilot operated valve?

A

Follows the rise and fall of the liquid column.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How does the evaporative condenser pump get its start?

A

Signal is received from discharge pressure control

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Does oil cooling take priority over everything else? T or F

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is double indirect system?

A

Primary loop with two secondary loops

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is a reverse return system?

A

Keeps every pass across the rink the same distance to keep the pressure drop approximately the same.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

25 ppm TLV/TWA

A

Exposure to 25 ppm for an 8 hour work day and a 40 hour work

week is permissible

18
Q

35 ppm ST/STEL

A

Exposure to 35 ppm must be limited to no more than 15 minutes

19
Q

300 ppm IDLH

A

Exposure to 300 ppm is Immediately Dangerous to Life and Health

20
Q

For R-717 how many BTU’S for latent heat of evaporation?

A

575 btu/lbs

21
Q

Why is R717 such a good refrigerant?

A

Because of its
ability to absorb heat while passing through an
evaporator of a refrigeration system. Has no Global Warming Potential or Ozone
Depletion Potential.

22
Q

What level of toxicity and flammability is R717?

A

B2, it is toxic and has some flame propagation

23
Q

Would you need a bigger compressor for R717 in comparison to R404a?

A

Yes, the specific volume is much larger than R404a

24
Q

What happens in low alarm. (25ppm, lower than 35ppm)?

A
  • Initiates MUA and Exhaust Fan.
    • Will create a local alarm strobe/siren
    • Will not dial out to monitoring or emergency services to allow minor problems to be repaired
25
Q

What happens mid level (50ppm)?

A
  • MUA/Exhaust continue to operate
  • Local alarm strobe/siren continue to operate
  • Monitoring company notified
26
Q

What happens at high level alarm (200ppm)?

A
  • MUA/Exhaust continue to operate
  • Local alarm strobe/siren continue to operate
  • Monitoring company notified
  • Emergency Services notified
27
Q

Where is the alarm sensor located?

A

Sensor location 10 ft above finished floor or 10-30 cm from ceiling

28
Q

How many air changes need to happen in the mechanical room?

A

15 air changes per hour

29
Q

How many pounds of water to one pound of ammonia in a deluge tank?

A

8lbs of water to 1lb of ammonia

30
Q

What is different about the TX valve in DX ammonia system?

A

Has a 2 stage pressure drop to reduce wear from flashing

31
Q

Why does the DX coil have to be large in ammonia?

A

To be able to superheat the refrigerant leaving the evaporator

32
Q

How far does the relief pipe need to be pipe according to B52?

A

15ft above the roof or 25ft away from the building or windows

33
Q

How high does the emergency valve/fire box need to be installed B52?

A

No less than 7ft

34
Q

What’s the most popular method of freezing?

A

Air blast freezing

35
Q

How is most industrial compressors, evaporators, and condensers piped?

A

In parallel

36
Q

What is a multi stage or compound system?

A

Refrigerant flows in series through 2 or more compressors. Suction of the high side is discharge of low stage.

37
Q

What temp do you use a compound system?

A

-10C 15F

38
Q

How is de-superheating accomplished?

A

Using an inter cooler between compressors

39
Q

What are the 2 types for feeding the evaporator?

A

Gravity flooded and liquid over feed

40
Q

How is liquid feed different from gravity flooded?

A

You need a pump and a low pressure receiver