INDOOR ENVIRONMENTAL QUALITY Flashcards
PEREQUISITE Minimum Indoor Air Quality Performance
REQUIRMENT (2)
Meet the requirements for both ventilation and monitoring.
PEREQUISITE Environmental Tobacco Smoke Control
INTENT
To prevent or minimize exposure of building occupants, indoor surfaces, and ventilation air distribution systems to environmental tobacco smoke.
PEREQUISITE Environmental Tobacco Smoke Control
REQUIREMENTS OPTION 1
Locate the project in a building that prohibits smoking by all occupants and users both inside the building
and outside the building except in designated smoking areas located at least X from all
entries, outdoor air intakes, and operable windows. Also prohibit smoking outside the property line in
spaces used for business purposes.
Signage must be posted within Y of all building entrances indicating the no-smoking policy
X; 25 feet (7.5 meters)
Y ; 10 feet (3 meters)
PEREQUISITE Environmental Tobacco Smoke Control
REQUIREMENTS OPTION 2
Prohibit smoking in the project spaces.
Smoking must also be prohibited in all common areas used by the project occupants and any areas of the building served by the same HVAC system as the project.
If smoking is permitted in other areas of the building, ensure that ETS cannot migrate by either mechanical or natural ventilation into the project spaces.
Communicate the no-smoking policy to occupants of the project. Have in place provisions for enforcement or no-smoking signage
PEREQUISITE Environmental Tobacco Smoke Control
REQUIREMENTS
For this prerequisite smoking includes …3.
- tobacco smoke,
- combustion of cannabis and controlled substances
- electronic smoking devices.
PEREQUISITE Minimum Indoor Air Quality Performance
Ventilation
Mechanically Ventilated Spaces
2 cases
CASE 1. SYSTEMS ABLE TO MEET REQUIRED OUTDOOR AIRFLOW RATES
Case 2. Systems Unable to Meet Required Outdoor Airflow Rates
PEREQUISITE Minimum Indoor Air Quality Performance
Ventilation
Mechanically Ventilated Spaces
CASE 1. SYSTEMS ABLE TO MEET REQUIRED OUTDOOR AIRFLOW RATES
2 options (normes)
OPTION 1. ASHRAE STANDARD 62.1–2010
OPTION 2. CEN STANDARDS EN 15251–2007 AND EN 13779–2007
PEREQUISITE Minimum Indoor Air Quality Performance
Ventilation
Mechanically Ventilated Spaces
Case 2. Systems Unable to Meet Required Outdoor Airflow Rates
If meeting the outdoor airflow rates in Case 1 is not feasible because of the physical constraints of the existing ventilation system, complete an engineering assessment of the system’s maximum outdoor air delivery rate.
Supply the maximum possible to reach the minimum setpoint in Case 1 and not less than X of outdoor air per person.
X 10 cubic feet per minute (5 liters per second)
PEREQUISITE Minimum Indoor Air Quality Performance
Ventilation
NAturally Ventilated Spaces
2 normes
ASHRAE Standard 62.1–2010 or a local equivalent
Chartered Institution of Building Services Engineers (CIBSE) Applications Manual AM10, March 2005, Natural Ventilation
in Nondomestic Building
PEREQUISITE Minimum Indoor Air Quality Performance
Monitoring
Mechanically Ventilated Spaces
1 requirement
1 norme
provide a direct outdoor airflow measurement device capable of measuring the minimum outdoor air intake flow with an accuracy of +/–10% of the design minimum outdoor airflow rate, as defined by the ventilation requirements above. An alarm must indicate when the outdoor airflow value varies by 15% or more from the outdoor airflow setpoint.
ASHRAE Standard 62.1–2010
PEREQUISITE Minimum Indoor Air Quality Performance
Monitoring
Mechanically Ventilated Spaces
provide a direct outdoor airflow measurement device capable of measuring the minimum outdoor air intake flow with an accuracy of +/–X% of the design minimum outdoor airflow rate, as defined by the ventilation requirements above. An alarm must indicate when the outdoor airflow value varies by Y% or more from the outdoor airflow setpoint.
X 10%
Y 15%
PEREQUISITE Minimum Indoor Air Quality Performance
Monitoring
Naturally Ventilated Spaces
3 REQUIREMENTS (1 NORME)
- Provide a direct exhaust airflow measurement device capable of measuring the exhaust airflow with an
accuracy of +/–10% of the design minimum exhaust airflow rate. An alarm must indicate when airflow values vary by 15% or more from the exhaust airflow setpoint.
·2· Provide automatic indication devices on all natural ventilation openings intended to meet the minimum
opening requirements. An alarm must indicate when any one of the openings is closed during occupied
hours.
·3· Monitor carbon dioxide (CO2) concentrations within each thermal zone. CO2 monitors must be between
3 and 6 feet (900 and 1 800 millimeters) above the floor and within the thermal zone. CO2 monitors must
have an audible or visual indicator or alert the building automation system if the sensed CO2 concentration
exceeds the setpoint by more than 10%. Calculate appropriate CO2 setpoints by using the methods in
ASHRAE 62.1–2010, Appendix C.
PEREQUISITE Minimum Indoor Air Quality Performance
Monitoring
Naturally Ventilated Spaces
Provide a direct exhaust airflow measurement device capable of measuring the exhaust airflow with an
accuracy of +/–X% of the design minimum exhaust airflow rate. An alarm must indicate when airflow values vary by Y% or more from the exhaust airflow setpoint.
·· Provide automatic indication devices on all natural ventilation openings intended to meet the minimum
opening requirements. An alarm must indicate when any one of the openings is closed during occupied
hours.
·· Monitor carbon dioxide (CO2) concentrations within each thermal zone. CO2 monitors must be between
Z above the floor and within the thermal zone. CO2 monitors must have an audible or visual indicator or alert the building automation system if the sensed CO2 concentration exceeds the setpoint by more than A%. Calculate appropriate CO2 setpoints by using the methods in B
X 10%
Y : 15%
Z : 3 and 6 feet (900 and 1 800 millimeters)
A : 10%
B : ASHRAE 62.1–2010, Appendix C.
CREDIT Enhanced Indoor Air
Quality Strategies
2 OPTIONS
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
Mechanically ventilated spaces 3
A. entryway systems;
B. interior cross-contamination prevention; and
C. filtration.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
Naturally ventilated spaces: 2
A. entryway systems; and
D. natural ventilation design calculations.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
Mixed-mode systems: 5
A. entryway systems;
B. interior cross-contamination prevention;
C. filtration;
D. natural ventilation design calculations; and
E. mixed-mode design calculations.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
A. Entryway Systems 2
Install permanent entryway systems at least 10 feet (3 meters) long in the primary direction of travel
Maintain all on a weekly basis.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
B. Interior Cross-Contamination Prevention : 4
- using the exhaust rates determined in EQ
Prerequisite Minimum Indoor Air Quality Performance or a minimum of 0.50 cfm per square foot (2.54 l/s per squaremeter), - to create negative pressure with respect to adjacent spaces when the doors to the room are closed.
- For each of these spaces, provide self-closing doors 4. and deck-to-deck partitions or a hard-lid ceiling.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
C. Filtration A OU B
A. (MERV) of 13 or higher, in accordance with ASHRAE Standard 52.2–2007;
or
·· Class F7 or higher as defined by CEN Standard EN 779–2002, Particulate Air Filters for General Ventilation, Determination of the Filtration Performance.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
B. Interior Cross-Contamination Prevention :
using the exhaust rates determined in EQ
Prerequisite Minimum Indoor Air Quality Performance or a minimum of X (volume)
X 0.50 cfm per square foot (2.54 l/s per squaremeter),
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
D. Natural Ventilation Design Calculations
NORME
Chartered Institution
of Building Services Engineers (CIBSE) Applications Manual AM10, March 2005, Natural Ventilation in Non-
Domestic Buildings, Section 2.4.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 1. ENHANCED IAQ STRATEGIES (1 POINT)
E. Mixed-Mode Design Calculations
NORME
CIBSE Applications Manual 13–2000, Mixed
Mode Ventilation.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
Mechanically ventilated spaces (select X): 4
X : 1
A. exterior contamination prevention;
B. increased ventilation;
C. carbon dioxide monitoring; or
D. additional source control and monitoring
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
Naturally ventilated spaces (select X) : 3
X 1
A. exterior contamination prevention;
D. additional source control and monitoring; or
E. natural ventilation room by room calculations.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
Mixed-mode systems (select X) : 4
X 1
A. exterior contamination prevention;
B. increased ventilation;
D. additional source control and monitoring; or
E. natural ventilation room-by-room calculations.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
A. Exterior Contamination Prevention
1 EXPLICATION
1 NORME - 3 MAXIMUM
Design the project to minimize and control the entry of pollutants into the building
National Ambient Air Quality Standards (NAAQS)
Allowable annual average
OR
8-hour or 24-hour average where an annual
standard does not exist
OR
Rolling 3-month average
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
B. Increased Ventilation
Increase breathing zone outdoor air ventilation rates to all occupied spaces by at least 30% above the minimum rates as determined in EQ Prerequisite Minimum Indoor Air Quality Performance.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
C. Carbon Dioxide Monitoring
Monitor CO2 concentrations within all densely occupied spaces. CO2 monitors must be between 3 and 6 feet (900 and 1 800 millimeters) above the floor. CO2 monitors must have an audible or visual indicator or alert the building automation system if the sensed CO2 concentration exceeds the setpoint by more than 10%. Calculate appropriate CO2 setpoints using methods in ASHRAE 62.1–2010, Appendix C.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
C. Carbon Dioxide Monitoring
Monitor CO2 concentrations within all densely occupied spaces. CO2 monitors must be between X above the floor. CO2 monitors must have an audible or visual indicator or alert the building automation system if the sensed CO2 concentration exceeds the setpoint by more than Y%. Calculate appropriate CO2 setpoints using methods in Z
X 3 and 6 feet (900 and 1 800 millimeters)
Y : 10
Z ASHRAE 62.1–2010, Appendix C.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
D. Additional Source Control and Monitoring
For spaces where air contaminants are likely, evaluate potential sources of additional air contaminants besides CO2. Develop and implement a materials-handling plan to reduce the likelihood of contaminant release. Install monitoring systems with sensors designed to detect the specific contaminants. An alarm must indicate any unusual or unsafe conditions.
CREDIT Enhanced Indoor Air
Quality Strategies
OPTION 2. ADDITIONAL ENHANCED IAQ STRATEGIES
E. Natural Ventilation Room-by-Room Calculations
NORME
Follow CIBSE AM10, Section 4, Design Calculations, to predict that room-by-room airflows will provide effective
natural ventilation.
CREDIT : Low-Emitting Materials
OPTION 1. PRODUCT CATEGORY CALCULATIONS
Compliant categories - Points
Compliant categories - Points
3 1
5 2
6 3
CREDIT : Low-Emitting Materials
OPTION 2. BUDGET CALCULATION METHOD
Percentage of total - Points
5 CATÉGORIES
DÉTAIL IMPORTANT
Percentage of total - Points
≥ 50% and < 70% 1
≥ 70% and < 90% 2
≥ 90% 3
The budget method organizes the building interior into five assemblies:
·· flooring;
·· ceilings;
·· walls;
·· thermal and acoustic insulation;
·· furniture; and
** Walls, ceilings, and flooring are defined as building interior products; each layer of the assembly, including paints, coatings, adhesives, and sealants, must be evaluated for compliance. Insulation is tracked separately.
CREDIT : Low-Emitting Materials
OPTION 1. PRODUCT CATEGORY CALCULATIONS
Interior paints and coatings applied
on site 2
At least 90%, by volume, (CDPH) for
emissions; 100% for VOC
content (CARB 2007 OU SCAQMD 1113)
CREDIT : Low-Emitting Materials
OPTION 1. PRODUCT CATEGORY CALCULATIONS
Interior adhesives and sealants
applied on site (including flooring
adhesive) : 2
At least 90%, by volume, (CDPH) for
emissions; 100% for VOC
content (SCAQMD 1168)
CREDIT : Low-Emitting Materials
OPTION 1. PRODUCT CATEGORY CALCULATIONS
Flooring 1
100% CDPH
CREDIT : Low-Emitting Materials
OPTION 1. PRODUCT CATEGORY CALCULATIONS
Composite wood
1,
2.
3. (abcd)normes
100% Composite Wood Evaluation
- low formaldehyde emissions that meet the California Air Resources Board ATCM for formaldehyde
requirements - for ultra-low-emitting formaldehyde (ULEF) resins or no added formaldehyde resins.
- not to exceed a concentration limit of 0.05 ppm of
formaldehyde as tested either following
A. EN-717-1:2004, following
B. ISO 16000 or following
C. CEN/TS 16516: 2013
D. either in conjunction with AgBB or with Belgian or French legislation on VOC emission class labeling.
CREDIT : Low-Emitting Materials
OPTION 1. PRODUCT CATEGORY CALCULATIONS
Ceilings, walls, thermal, and acoustic
insulation 1
100% CDPH
CREDIT : Low-Emitting Materials
OPTION 1. PRODUCT CATEGORY CALCULATIONS
Furniture : 1
90% BY COST Furniture Evaluation
ANSI/BIFMA Standard Method M7.1–2011
CREDIT : Construction Indoor Air Quality
Management Plan
NORME
NORME FILTRES 2
Sheet Metal and Air Conditioning National Contractors Association (SMACNA)
ASHRAE 52.2–2007
CEN Standard EN 779–2002
CREDIT : Construction Indoor Air Quality
Management Plan
4
- Protect absorptive materials .
- (MERV) of 8, are installed at each return air grille and return or transfer duct inlet opening such that there is no bypass around the filtration media.
- Immediately before occupancy, replace all filtration media
- Prohibit the use of tobacco products inside the building and within 25 feet (7.5 meters) of the building entrance during construction.
CREDIT : Construction Indoor Air Quality
Management Plan
SMACNA GUIDELINES 5
- HVAC protection
- Source control. Keep sources of contaminants out of the building and have a plan to eliminate any that are
introduced.
3.Pathway interruption. Prevent circulation of contaminated air when cutting concrete or wood, sanding drywall,
installing VOC-emitting materials, or performing other activities that affect IAQ in other work spaces - Housekeeping. Maintaining a clean job site results in fewer IAQ contaminants to manage
- Scheduling. Sequence construction activities to reduce air quality problems in new construction projects. For major
renovations, coordinate construction activities to minimize or eliminate disruption of operations in occupied areas.
CREDIT : Indoor Air Quality
Assessment
OPTION 1
PATH 1 -2
OPTION 2
OPTION 1. FLUSH-OUT (1 POINT)
Path 1. Before Occupancy
Path 2. During Occupancy
OPTION 2. AIR TESTING (2 POINTS)
CREDIT : Indoor Air Quality
Assessment
OPTION 1. FLUSH-OUT (1 POINT)
Path 1. Before Occupancy
Install new filtration media and perform a building flush-out by supplying a total air volume of 14,000 cubic feet of outdoor air per square foot (4 267 140 liters of outdoor air per square meter) of gross floor area while maintaining an internal temperature of at least 60°F (15°C) and no higher than 80°F (27°C) and relative humidity no higher than 60%.
CREDIT : Indoor Air Quality
Assessment
OPTION 1. FLUSH-OUT (1 POINT)
Path 1. Before Occupancy
Install new filtration media and perform a building flush-out by supplying a total air volume of X of gross floor area while maintaining an internal temperature of Y and relative humidity no higher than Z%.
X 14,000 cubic feet of outdoor air per square foot (4 267 140 liters of outdoor air per square meter)
Y at least 60°F (15°C) and no higher than 80°F (27°C)
Z : 60%
CREDIT : Indoor Air Quality
Assessment
OPTION 1. FLUSH-OUT (1 POINT)
Path 2. During Occupancy
- If occupancy is desired before the flush-out is completed, the space may be occupied only after delivery of a minimum of 3,500 cubic feet of outdoor air per square foot (1 066 260 liters of outdoor air per square meter) of gross floor area while maintaining an internal temperature of at least 60°F (15°C) and no higher than 80°F (27°C) and relative humidity no higher than 60%.
- Once the space is occupied, it must be ventilated at a minimum rate of 0.30 cubic foot per minute (cfm) per
square foot of outdoor air (1.5 liters per second per square meter of outdoor air) or the design minimum outdoor air rate determined in EQ Prerequisite Minimum Indoor Air Quality Performance, whichever is greater. During each day of the flush-out period, ventilation must begin at least three hours before occupancy and continue during occupancy.
These conditions must be maintained until a total of 14,000 cubic feet per square foot of outdoor air (4 270 liters of outdoor air per square meter) has been delivered to the space.
CREDIT : Indoor Air Quality
Assessment
OPTION 1. FLUSH-OUT (1 POINT)
Path 2. During Occupancy
- If occupancy is desired before the flush-out is completed, the space may be occupied only after delivery of a minimum of A of gross floor area while maintaining an internal temperature of B and relative humidity no higher than C %.
- Once the space is occupied, it must be ventilated at a minimum rate of D or the design minimum outdoor air rate determined in EQ Prerequisite Minimum Indoor Air Quality Performance, whichever is greater. During each day of the flush-out period, ventilation must begin at least three hours before occupancy and continue during occupancy. These conditions must be maintained until a total of E has been delivered to the space.
A 3,500 cubic feet of outdoor air per square foot (1 066 260 liters of outdoor air per square meter)
B at least 60°F (15°C) and no higher than 80°F (27°C)
C 60%
D : 0.30 cubic foot per minute (cfm) per
square foot of outdoor air (1.5 liters per second per square meter of outdoor air)
E : 14,000 cubic feet per square foot of outdoor air (4 270 liters of outdoor air per square meter)
CREDIT : Indoor Air Quality
Assessment
OPTION 2. AIR TESTING (2 POINTS)
NORME 3 CHOIX + LABO CERTIFIÉ
- Use current versions of ASTM standard methods,
- EPA compendium methods, or
- ISO methods, as indicated.
Laboratories that conduct the tests for chemical analysis of formaldehyde and volatile organic compounds must be accredited under ISO/IEC 17025 for the test methods they use
CREDIT : Thermal Comfort
2 REQUIREMENTS
Thermal Comfort Design
Thermal Comfort Control
CREDIT : Thermal Comfort
Thermal Comfort Design
2 OPTIONS (NORME)
1.
2.1
2.2
Thermal Comfort Control
…..
ADJUSTE 4 parameter
OPTION 1. ASHRAE STANDARD 55-2010
OPTION 2. ISO AND CEN STANDARDS
2.1 ISO 7730:2005,
2.2 CEN Standard EN 15251:2007
Provide individual thermal comfort controls for at least 50% of individual occupant spaces. Provide group thermal comfort controls for all shared multioccupant spaces.
air temperature, radiant temperature, air speed, and
humidity.
CREDIT : Thermal Comfort
2 EXCEPTIONS
HOSPITALITY ONLY
Guest rooms not included in the credit calculations.
RETAIL ONLY
Meet the above requirements for at least 50% of the individual occupant spaces in office and administrative areas.
CREDIT Interior Lighting
CI AND HOPSPITALITY
2 OPTIONS
OPTION 1. LIGHTING CONTROL (1 POINT)
OPTION 2. LIGHTING QUALITY (1 POINT)
CREDIT Interior Lighting
CI AND HOPSPITALITY
OPTION 1. LIGHTING CONTROL (1 POINT)
EXEPTION
For at least 90% of individual occupant spaces, provide individual lighting controls that enable occupants to adjust the lighting to suit their individual tasks and preferences, with at least three lighting levels or scenes
Guest rooms not included in the credit calculations.
CREDIT Interior Lighting
CI AND HOPSPITALITY
OPTION 1. LIGHTING CONTROL (1 POINT)
For at least X% of individual occupant spaces, provide individual lighting controls that enable occupants to adjust the lighting to suit their individual tasks and preferences, with at least three lighting levels or scenes (on, off, midlevel). Midlevel is Y of the maximum illumination level (not including daylight contributions).
X 90
Y 30% to 70%
CREDIT Interior Lighting
CI AND HOPSPITALITY
Choose X of the following strategies 8
X 4
A. For all regularly occupied spaces, use light fixtures with a luminance of less than 2,500cd/m2 between 45 and 90 degrees from nadir.
B. For the entire project, use light sources with a CRI of 80 or higher.
C. For at least 75% of the total connected lighting load, use light sources that have a rated life of at least 24,000 hours.
D. Use direct-only overhead lighting for 25% or less of the total connected lighting load for all regularly occupied spaces.
E. For at least 90% of the regularly occupied floor area, meet or exceed surface reflectance: 85% for ceilings, 60% for walls, and 25% for floors.
F. If furniture is included in the scope of work, select furniture finishes to meet or exceed the surface reflectance: 45% for work surfaces, and 50% for movable partitions.
G. For at least 75% of the regularly occupied floor area, meet a ratio of average wall surface illuminance that does not exceed 1:10.
H. For at least 75% of the regularly occupied floor area, meet a ratio of average ceiling illuminance that does not exceed 1:10.
CREDIT Interior Lighting
CI AND HOPSPITALITY
Choose 4 of the following strategies 8
A. For all A, use light fixtures with a luminance of less than B between C from nadir.
B. For the D, use light sources with a CRI of E or higher.
C. For at least F% of the total connected lighting load, use light sources that have a rated life of at least G hours.
D. Use direct-only overhead lighting for H% or less of the total connected lighting load for all regularly occupied spaces.
A regularly occupied spaces
B 2,500cd/m2
C 45 and 90 degrees
D The entire project
E CRI80
F 75%
G 24,000H
H 25
CREDIT Interior Lighting
CI AND HOPSPITALITY
Choose 4 of the following strategies 8
E. For at least A% of the regularly occupied floor area, meet or exceed surface reflectance: B% for ceilings, C% for walls, and D% for floors.
F. If furniture is included in the scope of work, select furniture finishes to meet or exceed the surface reflectance: E% for work surfaces, and F% for movable partitions.
G. For at least G% of the regularly occupied floor area, meet a ratio of average wall surface illuminance that does not exceed H.
H. For at least I% of the regularly occupied floor area, meet a ratio of average ceiling illuminance that does not exceed J
A 90%
B : 85%
C: 60%
D: 25%
E : 45%
F: 50%
G 75%
H 1:10
I 75%
J 1:10
CREDIT Interior Lighting
RETAIL
For at least 90% of the individual occupant spaces in office and administrative areas, provide individual lighting controls.
In sales areas, provide controls that can reduce the ambient light levels to a midlevel (30% to 70% of the maximum illumination level not including daylight contributions).
CREDIT Daylight
REQUIREMENT +
3 OPTIONS
Provide manual or automatic (with manual override) glare-control devices for all regularly occupied spaces.
OPTION 1. SIMULATION: SPATIAL DAYLIGHT AUTONOMY AND ANNUAL SUNLIGHT
EXPOSURE
OPTION 2. SIMULATION: ILLUMINANCE CALCULATIONS
OPTION 3. MEASUREMENT
CREDIT Daylight
OPTION 1. SIMULATION: SPATIAL DAYLIGHT AUTONOMY AND ANNUAL SUNLIGHT
EXPOSURE
sDA (for regularly occupied floor area) Points
sDA (for regularly occupied floor area) Points
55% 2
75% 3
CREDIT Daylight
OPTION 1. SIMULATION: SPATIAL DAYLIGHT AUTONOMY AND ANNUAL SUNLIGHT
EXPOSURE
2 REQUIS
- Demonstrate through annual computer simulations that spatial daylight autonomy300/50% (sDA300/50%) of at least 55%, 75%, or 90% is achieved. Use regularly occupied floor area
- Demonstrate through annual computer simulations that annual sunlight exposure1000,250 (ASE1000,250) of no more than 10% is achieved.Use the regularly occupied floor at a work plane height of 30 inches
CREDIT Daylight
OPTION 2. SIMULATION: ILLUMINANCE CALCULATIONS
Percentage of regularly occupied floor area Points
Percentage of regularly occupied floor area Points
75% 1
90% 2
CREDIT Daylight
OPTION 2. SIMULATION: ILLUMINANCE CALCULATIONS
REQUIS
Demonstrate through computer modeling that illuminance levels will be between 300 lux and 3,000 lux for 9 a.m. and 3 p.m., both on a clear-sky day at the equinox, for the floor area
CREDIT Daylight
OPTION 3. MEASUREMENT
Percentage of regularly occupied floor area Points
Percentage of regularly occupied floor area Points
75 2
90 3
CREDIT Daylight
OPTION 3. MEASUREMENT
REQUIS
Achieve illuminance levels between 300 lux and 3,000 lux for the floor area
CREDIT Quality Views
- Achieve a direct line of sight to the outdoors via vision glazing for A % of all B
- Additionally, C% of all regularly occupied floor area must have at least D of the following four kinds of views:
·A· multiple lines of sight to vision glazing in different directions at least E degrees apart;
·B· views that include at least two of the following: 3
·C· unobstructed views located within the distance of F times the head height of the vision glazing; and
·D· views with a view factor of G or greater,
Views into interior atria may be used to meet up to H% of the required area.
Include any permanent interior obstructions and moveable furniture and partitions.
A 75%
B regularly occupied floor area.
C 75%
D 2
E 90
(1) flora, fauna, or sky;
(2) movement; and
(3) objects at least 25 feet (7.5 meters) from the exterior of the glazing;
F 3
G 3
H : 30%
CREDIT Quality Views
2 REQUIS
- Achieve a direct line of sight to the outdoors via vision glazing for 75% of all regularly occupied floor area.
- Additionally, 75% of all regularly occupied floor area must have at least two of the following four kinds of views:
CREDIT Acoustic Performance
For all X, meet the following requirements, as applicable, 4
X occupied spaces
1.HVAC background noise,
2. sound isolation,
3. reverberation time,
4. sound reinforcement and masking
CREDIT Acoustic Performance
HVAC Background Noise
…
2 NORMES
NORME MESUREMENT
NORME HVAC NOISE LEVEL
Achieve maximum background noise levels from heating, ventilating, and air conditioning (HVAC) systems per
1.2011 ASHRAE Handbook, HVAC Applications,
2. AHRI Standard 885-2008,
For measurements, use a sound level meter that conforms to ANSI S1.4 for type 1 (precision) or type 2 (general purpose)
Comply with design criteria for HVAC noise levels resulting from the sound transmission paths listed in ASHRAE 2011 Applications Handbook,
CREDIT Acoustic Performance
HVAC Background Noise
Achieve maximum background noise levels from ABC (HVAC) systems per D OR E or a local equivalent.
Calculate or measure sound levels.
For measurements, use a sound level meter that conforms to F for type 1 (precision) or type 2 (general
purpose) sound measurement instrumentation, or a local equivalent.
Comply with design criteria for HVAC noise levels resulting from the sound transmission paths listed in G or a local equivalent.
ABC heating, ventilating, and air conditioning
D 2011 ASHRAE Handbook, HVAC Applications, Chapter 48, Table 1;
E : AHRI Standard 885-2008, Table 15;
F ANSI S1.4
G ASHRAE 2011 Applications Handbook, Table 6;
CREDIT Acoustic Performance
Sound Transmission
Adjacency combinations : STCC
Residence , hotel or motel room / IBID :
Residence, hotel or motel room / Common hallway, stairway :
Residence, hotel or motel room / Retail
Adjacency combinations : STCC
Residence , hotel or motel room / IBID : 55
Residence, hotel or motel room / Common hallway, stairway : 50
Residence, hotel or motel room / Retail 60
CREDIT Acoustic Performance
Sound Transmission
Retail / Retail
Retail / Retail 50
CREDIT Acoustic Performance
Sound Transmission
Standard office/ Standard office
Executive office/ Executive office
Conference room/ Conference room
Office, conference room/ Hallway, stairway
Standard office/ Standard office 45
Executive office/ Executive office 50
Conference room/ Conference room 50
Office, conference room/ Hallway, stairway 50
CREDIT Acoustic Performance
Sound Transmission
Mechanical equipment room / Occupied area
Mechanical equipment room / Occupied area 60
CREDIT Acoustic Performance
Reverberation Time
Apartment and condominium
< 0.6
CREDIT Acoustic Performance
Reverberation Time
Hotel/motel
Individual room or suite
Meeting or banquet room
Individual room or suite < 0.6
Meeting or banquet room < 0.8
CREDIT Acoustic Performance
Reverberation Time
Office building
Executive or private office
Conference room
Teleconference room
Open-plan office without sound masking
Open-plan office with sound masking
Executive or private office < 0.6
Conference room < 0.6
Teleconference room < 0.6
Open-plan office without sound masking < 0.8
Open-plan office with sound masking 0.8
CREDIT Acoustic Performance
Reverberation Time
Courtroom
Unamplified speech
Amplified speech
Unamplified speech < 0.7
Amplified speech < 1.0
CREDIT Acoustic Performance
Reverberation Time
Laboratories
Testing or research with minimal speech
communication
Extensive phone use and speech communication
Testing or research with minimal speech
communication
< 1.0
Extensive phone use and speech communication < 0.6
CREDIT Acoustic Performance
Reverberation Time
Library
< 1.0
CREDIT Acoustic Performance
Reverberation Time
Indoor stadium, gymnasium
Gymnasium and natatorium
Large-capacity space with speech amplification
Gymnasium and natatorium < 2.0
Large-capacity space with speech amplification < 1.5
CREDIT Acoustic Performance
Reverberation Time
Classroom
< 0.6
CREDIT Acoustic Performance
Sound Reinforcement (1) and Masking Systems (1)
Sound Reinforcement
For all large conference rooms and auditoriums seating more than 50 persons, evaluate whether sound
reinforcement and AV playback capabilities are needed.
Masking Systems
For projects that use masking systems, the design levels must not exceed 48 dBA. Ensure that loudspeaker coverage
provides uniformity of +/–2 dBA and that speech spectra are effectively masked.
CREDIT Acoustic Performance
Sound Reinforcement
For all large conference rooms and auditoriums seating more than A persons, evaluate whether sound reinforcement and AV playback capabilities are needed.
If needed, the sound reinforcement systems must meet the following criteria:
·1· Achieve a speech transmission index (STI) of at least B or common intelligibility scale (CIS) rating of at
least C at representative points within the area of coverage to provide acceptable intelligibility.
·2· Have a minimum sound level of D dBA.
·3· Maintain sound-level coverage within +/–E dB at the F Hz octave band throughout the space.
Masking Systems
For projects that use masking systems, the design levels must not exceed G dBA. Ensure that loudspeaker coverage provides uniformity of +/–H dBA and that speech spectra are effectively masked.
A 50 PERSON
B 0.60
C 0.77
D 70 DBA
E 3 DB
F 2000 HZ
G 48 DBA
H 2 DBA
CREDIT Acoustic Performance
Sound Reinforcement and Masking Systems
Sound Reinforcement
If needed, the sound reinforcement systems must meet the following criteria: 3
- Achieve a speech transmission index (STI) of at least 0.60 or common intelligibility scale (CIS) rating of at
least 0.77 at representative points within the area of coverage to provide acceptable intelligibility.
·2 Have a minimum sound level of 70 dBA.
·3· Maintain sound-level coverage within +/–3 dB at the 2000 Hz octave band throughout the space.