How to Perform Residential Electrical Inspections Flashcards

1
Q

Modern bathroom receptacles are typically on _________ circuits.

A

20-amp, GFCI-protected

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The purpose of __________ is to ensure the electrical continuity of the fault current path, to provide the capacity and ability to conduct safely any fault current likely to be imposed, and to aid in the operation of the over-current protection device.

A

Bonding

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Service drops should not pass closer than ____ feet over the ridge of a sloped roof

A

3ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Any GFCI breaker or receptacle that _____ should be written up as in need of immediate replacement.

A

fails to trip and reset properly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The service-entrance conductors (blue arrow) are the service conductors located between the terminals of the service equipment (main disconnect) and a point usually outside the building, clear of building walls, where they are joined by a tap or splice (_____ arrows) to the service drop or overhead service conductors (red arrows).

A

Orange

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Most residential services are ___________.

A

120/240-‐volt services

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The minimum cable size for a service entrance for a 200-amp supply is ______________.

A

2/0 copper or 4/0 aluminum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Breakers that show evidence of scorching should be reported as ___________.

A

a safety hazardous defect

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

For a 12-gauge copper wire, the maximum overcurrent protection rating is _____ amps.

A

20amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

For a 14-gauge copper wire, the maximum overcurrent protection rating is _____ amps.

A

15amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The maximum breaker rating must _____ the allowable ampacity of the conductor.

A

not exceed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

A service entrance with ________ connected conductor(s) is a 3-phase supply.

A

Four

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

A service drop should be at least ________ away from any nearby trees.

A

5 - 6 ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The minimum conductor size for a ______-amp service is 4-awg copper or 2-awg aluminum.

A

100

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

If a flat roof is used as a garden, the minimum clearance required for the service drop is _______ feet.

A

10ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Electrical service panels should be in a clear space measuring

A

30” wide by 78” high by 36” deep

17
Q

Water dripping from an electrical panel should be __________________.

A

tagged as an immediate hazard and deferred to an electrician

18
Q

A bonding connection ______________________ connect the grounding bus to the electrical enclosure.

A

Should