High Temp Hot Water Systems Flashcards
At what temperature does a high temperature hot water system start?
177°C
What is the range in temperature for a high temperature hot water system?
177°C to 232°C
What temperatures do medium temperature Hot water systems Generally operate at?
121°C to 177°C
What specifications are high temperature hot water boiler set to?
ASME section one
What type of boiler is used for high temperature Hot water service?
Water tube
Where is the return water directed in a high temperature Hot water system?
Below the boiler waterline
What does the feed water pass through upon entering the boiler?
Expansion drum.
What are the three advantages of using a steam boiler for high temperature hot water systems?
- Existing steam boilers can be readily converted.
- You can change the steam and hot water ratios to suit demands.
- Temporary loss of pressure doesn’t affect the system so long as the water level is maintained.
Are threaded fittings on HTHW systems permitted?
No
How do HTHW systems deal with system expansion, and contraction?
Through the use of steam for pressurizing, the expansion drum or the use of a nitrogen or steam pressured cascade heater, which functions as an expansion drum
Is a nitrogen padded expansion drum installed horizontally, or vertically and why?
A nitrogen padded expansion drum is installed vertically to decrease the interface area between the gas and the water
When a steam pad is used to pressurize the system is the expansion drum set horizontally, or vertically and why?
Horizontally and elevated well above the circulating pumps to prevent cavitation.
What are some advantages of an HTHW system over a steam system?
- Less water treatment is required.
- They have smaller boiler feed pumps.
- Piping elevation changes are not a problem as no traps are required however, events are required at the Highpoints.
- There is less internal corrosion because less makeup water is required.
- Larger temp differentials allow for use of smaller heat units and smaller pipe sizes.
- Historically they have lower maintenance costs.
What are the disadvantages of HTHW over steam systems?
- The system takes longer to heat up, especially from cold start after shut down.
- Standby pumps are required.
- Circulating pumps must operate continuously.
- Sudden leaks will drop pressure which result in the formation of flash steam. Flash steam can cause water hammer, and cavitation in other parts of the system.
- Pump selection and trim are more difficult. High temperature water is classified as a hard to hold fluid.
- Pipe sizing, and design layout are much more critical to prevent noise and cavitation.
How is circulation accomplished in an HTHW generator?
Thermal currents of flow from the circulating pumps. Heat absorbing tubes are piped to upflow water and downcomer are insulated to protect from hot gases in the unit.
Which gas is preferred to pressurize the expansion drum?
Nitrogen
Why is compressed air not used to pressurize the expansion drum?
Oxygen would adversely affect the system components
Does water or steam have more thermal capacity by volume?
Water
Why is a manual vent required on an HTHW generator?
To vent air
What is the minimum designation and grade of pipe used for an HTHW system?
ASTM designation a – 53, grade a, no less than schedule 40 pipe.