high rise office Flashcards

0
Q

After fire floor has been determined the hvac zones serving other floors shall have what done?

A

After the fire floor has been adequately determined, all HVAC zones that do not include the fire area shall have their supply fans activated. This will supply fresh outside air to these zones, pressurizing these zones and limiting the spread of smoke. It will also supply fresh outside air to any occupants on the floors in these zones.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

How do you place HVAC systems in non circulating mode?

A

All the HVAC systems shall be placed in the non-circulating mode by:

A. Opening all outside air supply dampers.

B. Closing all mixing dampers.

C. Opening all exhaust dampers. (Figure 2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the requirements for installation of fire pumps under the 1968 code and under the 1938 code?

A

B. The 1968 Building code requires a manual fire pump to supplement the standpipe system in buildings over 300 feet high. The 1938 Building Code requires a manual fire pump in buildings over 250 high.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is an easy way to determine the discharge gauged on manual fire pump?

A

C. Locate the bypass valve (B) on the discharge side of the fire pump. The discharge side can be readily identified by examining the gauges. The discharge gauge is calibrated for higher pressures than the inlet gauge.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What position should the bypass valve be in?

A

D. The bypass valve should be in the closed position (stem in).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

If bypass valve is left open, how much will the efficiency of the pump be affected?

A

The efficiency of the pump will be affected if the bypass is open. A loss of 25% can be expected in an 8” riser and a loss of 45% can be expected in a 6” riser with the bypass open.

Note
You must notify building engineer if you were unable to determine bypass valve and therefore are unsure if it is open or closed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the fours yep procedure to start fire pumps?

A

Four step procedure for starting of fire pumps using the control panel. Remember acronym Kansas City baseball league.

OPERATION LOCATION
A. Close knife switch (1) to on position. (Figures 9, 10)
.
B. Close circuit breaker(s) (2) & power on light will glow.
.
C. Push starting button (3) & pump on light will glow. (Figures 9, 10)
.
D. Move selector lever (4) to desired position increasing pump speed and thereby increasing pressure.

The fire pumps should now be operating. If they have failed to start, the emergency power lever located at the panel shall be used. Push or pull to “on” position (5). (Figures 9, 10)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the recommended pump discharge pressures?

A

4.1.7

Recommended Pump Pressure
FIRE FLOORS	 PUMP DISCHARGE PRESSURE
Floors 1 to 10	         150 psi
Floors 11 to 20	         200 psi
Floors 21 to 30	 250 psi
Floors 31 to 40	 300 psi
Floors 41 to 50	 350 psi
Floors 51 to 60	 400 psi
Floors 61 to 70	 450 psi
Floors 71 to 80	 500 psi
Floors 81 to 90	 550 psi
Floors 91 to 100	 600 psi
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How do you shut down the pumps?

A

K. When the command to shut down the building fire pumps is received, and the engineer in charge is not available, the pumps are deactivated by reversing the starting procedure.

  1. Return pump position lever to lowest speed.
  2. Push “off” button.
  3. Open circuit breakers.
  4. Open knife switch (off position).
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What should be pressure be at the highest floor house outlet?

A

The building fire pumps shall be capable of delivering their rated capacity at a pressure of 50 psi at the highest floor hose outlet.

A relief valve is required at the fire pump limiting the pressure to 15 psi above that required to deliver its rated capacity at 50 psi to the highest floor outlet.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When shall a1076 be transmitted?

When shall a second alarm be transmitted?

A

A. A 10-76 signal shall be transmitted when a report of fire is confirmed.

Any fire in a high-rise office building which requires the stretching and operating of one hoseline will necessitate the use of All Hands.

B. A second alarm is warranted for any visible fire or smoke emanating through the exterior skin of the building or when a serious fire has been verified.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where does the third due ladder operate at a high rise office fire?

A
  1. The third arriving ladder company shall be assigned to search and evacuate the floor above the fire.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Where does the fourth due ladder-operate at a high rise office fire?

A
  1. The fourth arriving ladder company shall be assigned similarly, to operate on the upper floors and to initiate the search of the attack stairway.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

When would a fire branch generally be implemented to maintain control?

A

A rapidly expanding incident often presents span of control issues. These types of incidents require increasing numbers of units to be assigned. A Fire Branch may be implemented to address these span of control issues. Generally a Branch would be activated on the 2nd alarm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How may the second hose line be used ?

A

Considering all the above items, the placement of the second line may be used to:

A. Reinforce the position of the first line.

B. Protect the position of the first line.

C. Protect the search and evacuation of the fire floor.

D. Contain and confine fire spread and/or prevent fire from wrapping around the core and endangering operation of the first line.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Who controls all horizontal ventilation tactics at a 1076?

A

All horizontal ventilation tactics shall be controlled, communicated and coordinated by the IC.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What shall the fire sector/branch be equipped with?

A
  1. SCBA for all personnel required for the operations of this sector/branch.
  2. Copy of the floor plan.
  3. Fire Sector/Branch log. (Figure 14)
  4. Post Radio
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

In ICS who do leaders operate under and who do supervisors operate under?

Why are branches formed?

A

NOTE:
ICS Note
Leaders operate under Supervisors and Supervisors operate under Directors.

ICS Note
Branches are formed to address span of control issues. A Group Supervisor can supervise 3-7 units. If more units are used, a Branch should be established, and groups or sectors assigned to that Branch.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

The command channel shall be used between whom?

A

The command channel shall be used between the Fire Sector/Branch, Forward Staging Area, Forward Triage Area, and Search and Evacuation Group. Hard wire communications shall also be established.

19
Q

The fire sector shall establish the following communications link

A
  1. HT communications on the primary tactical channel with the units under his or her command. When the Fire Sector/Branch is established, units under its command shall not communicate with the ICP unless urgent.
  2. HT communications with the ICP on the command channel. Hard wire communications shall also be established.
  3. HT communication between the Fire Sector/Branch and the Forward Staging Area shall be conducted on the command channel.
  4. The Fire Sector Supervisor or Fire Branch Director shall operate on the primary tactical channel. His/her aide shall operate on the command channel.
20
Q

The SEA group shall establish the following communications link?

A
  1. HT communication with the units under his/her command on the secondary tactical channel. When the SAE Group is established, units assigned to the SAE Group shall switch to secondary tactical channel and shall not communicate with the ICP unless urgent.
  2. HT communications with the IC on the command channel. Hard wire communication shall also be established.
  3. The Search and Evacuation Group Supervisor shall operate on the secondary tactical channel. His/her aide shall monitor and operate on the command channel.
21
Q

E. The Forward Staging Area Manager shall establish the following communications network:

A
  1. HT communications with the ICP and the Fire Sector or Branch on the command channel. Hard wire communications shall also be established with the ICP.
  2. The Forward Staging Area Manager shall operate on the command channel. His/her aide shall monitor the primary tactical channel.
22
Q

The logistics chief is responsible for the following

A

E. Logistics Section Chief

  • Supervision of the Lobby Control Unit.
  • Supervision of the Communications Unit.
  • Supervision of the High-Rise Support Unit.
  • Supervision of the Systems Control Unit.
  • Supervision of the Rehabilitation Unit.
  • Responsible for all activities supporting the incident.
23
Q

What is the lobby control unit duties?

A

G. Lobby Control Unit

  • Recall, control, and operate elevators. Recall and search all elevator cars terminating at the lobby.
  • Establish and control all building access points and direct personnel to correct stair/elevator or route.
  • Direct building occupants and exiting personnel to proper ground level safe areas or routes.
24
Q

The systems control unit is responsible for

A

H. System Control Unit

  • Monitor and control the Class E communications system; the heating, ventilation, and air conditioning (HVAC) system and any other building systems as directed by the Incident Commander.
  • Evaluate communications systems for functionality and operability.

This includes the use of HTs, hardwire phones, cellular phones, post radios, cross-band repeaters and building repeaters.

25
Q

Where is forward triage area located?

A
  • Responsible for the prompt response to injured civilians and members.
  • Established in an environmentally safe location on a floor below the Forward Staging Area.
26
Q

Who initially establishes and staffs the incident command post?

A

A. The first arriving officer shall establish the ICP. In the event that he or she leaves the ICP before the arrival of a Chief Officer, he or she shall designate a member to staff the ICP, preferably the chauffeur of the first arriving ladder company. This member shall then note the units entering and leaving the lobby and their destination.

27
Q

how many units shall be at the forward staging area for support of fire sector?

A

C. At high-rise fires, consideration of resource availability and response time are important. At least three engines and two ladder companies shall be at the Forward Staging Area for immediate support of the Fire Sector/Branch. The SAE Group will require at least one unit for every five floors to be covered.

28
Q

How many cylinders shall be at forward staging area?

A

D. Supply sufficient spare SCBA cylinders to the Forward Staging Area to support operations. A supply of at least 20 spare SCBA cylinders shall be maintained at the Forward Staging Area.

29
Q

F. Ladder companies reporting to the Forward Staging Area shall bring with them the following equipment, unless otherwise directed:

A
  1. A SCBA for each member.
  2. Two sets of forcible entry tools and six-foot hooks.
  3. Search and utility ropes.
  4. A spare SCBA cylinder for each member.
30
Q

E. Engine companies reporting to the Forward Staging Area shall bring with them the following equipment unless otherwise directed:

A
  1. A SCBA for each member.
  2. A standpipe kit and a nozzle.
  3. A length of hose per firefighter.
  4. A spare SCBA cylinder for each member.
31
Q

Can a fixed stairwell pressurization system be augmented by fdny fans?

A

The fixed system should not be augmented by FDNY Positive Pressure Ventilation Fans. Augmentation can cause leakage which will reduce pressure in the stair shaft.

32
Q

true or false. If a fixed system stairwell pressurization is activated prior to our arrival the IC should have the system turned off.

A

False.
When operating in a building that has a fixed stairwell pressurization system that is activated, the IC shall continue operations with the system on.

33
Q

What is positive stack effect and when does it increase?

A

The positive stack effect is the upward movement of air in a vertical shaft.

Positive stack effect increases as the outside air temperature decreases in relation to the temperature inside the building.

34
Q

What is negative stack effect and when does it occur?

A

b. The negative stack effect is the downward movement of air in a vertical shaft.
4. Negative stack effect may occur when the outside temperature is greater than the temperature inside the building. Its possibility is greatest when the outside air temperature is above 90º F.

35
Q

Where is the forward triage area located?

A

• Established in an environmentally safe location on a floor below the Forward Staging Area.

36
Q

Stack effect becomes noticeable in buildings over ______ feet?

A
  1. Its effect becomes noticeable in buildings over 60 feet, and increases as the building’s height increases.
37
Q

The criteria for the location of the SAE Group Supervisor shall be dependent on the following:

A

A. Fire location and severity

B. HT effectiveness

C. If possible, the SAE Group Supervisor shall choose a location on a floor which is not serviced by the same bank of elevators as the fire floor and at least five floors above the fire floor. (Figure 18)

38
Q

The Forward Staging Area shall be established two floors below the original fire floor, when the following conditions permit:

A

A. Where there is adequate space to hold units and equipment in reserve.

B. Where the units have ready access to the Fire Sector/Branch and attack stairway(s).

C. That provides hard wire communications to the ICP.

D. That provides reliable HT communications between the Forward Staging Area and the Fire Sector/Branch, SAE Group and the ICP.

E. That is accessible to units reporting to it.

F. Area is a non-IDLH environment.

39
Q

Who provides for the transportation of injured members and civilians to the forward triage area?

A

The forward staging manager shall Provide for the transportation of injured members or building occupants to the Forward Triage Area or to the lobby.

40
Q

Where is the forward triage area located?

A

6.7.3

The FTA shall be established in an environmentally safe location on a floor below the Forward Staging Area. If conditions deteriorate on this floor, EMS personnel shall change locations. The IC shall be advised.

41
Q

In a class E building there should be a two way communication system between……..

A

C. Two-way communications between the fire command station and the following:

  1. Floor warden stations.
  2. Mechanical control center.
  3. Elevators.
  4. Air handling control rooms.
  5. Elevator machinery rooms.
42
Q

7.2.4

At least one manual fire alarm sending station shall be located in each path of escape in each story of a building. Additional stations shall be installed so that no point on any floor shall be more than 200 feet from the nearest station. The activation shall cause:

A. Automatic transmission to the Fire Department via a central station.

B. A visual and audible signal at the fire command station, mechanical control center and the regularly assigned location of the fire safety director.

C. Sounding of the alarm on the fire floor and the floor above.

A

.

43
Q

An approved combustion ionization detection device or a combination of an approved smoke detecting device and an approved fixed temperature thermostatic device shall be installed:

A. At each elevator landing, the activation of this device shall:

  1. Recall the elevators.
  2. Sound the fire alarm signal on the fire floor and the floor above.

NOTE:
In buildings built under the 2008 Building Code, the alarm will also sound on the floor below.
3. Cause a fire alarm signal to be transmitted to the Fire Department via a central station.

  1. Cause a fire alarm signal to be sounded at the fire command station, the mechanical control center and the regularly assigned location of the fire safety director.
  2. Stop the air supply into and the return air from the floor where activated.
  3. Activate the air exhaust fans and dampers in the smoke shaft or the pressurizing fans in the stair enclosure.
  4. Unlock the doors on the locked fail safe system.

B. Within the HVAC system, the activation of this device shall accomplish all of the actions listed in 7.2.5A with the exception of recalling the elevators.

The activation of a sprinkler water flow alarm shall accomplish all of the actions listed in Section 7.2.5A.

A

.

44
Q

How does the third due ladder access the floor above the fire?

A
  1. Proceed to the floor above the fire via a stairway other than the attack stairway.