Governor Actuator Cabinet Flashcards
A - H
Temperature Air Cooler 1 - 8
Scale: 0-55 C
Normal: 25 C
Alarm: 45 C
Gas filled bulb, Generator Housing, behind surface air cooler
I
Temperature Generator Upper Guide Bearing
Scale: 10-105 C
Normal: 45 C
Alarm: 70 C
Gas filled bulb, imbedded in the upper guide bearing
J
Temperature Thrust Bearing
Scale: 10-105 C
Normal: 50 C
Alarm: 70 C
Gas filled bulb, imbedded in the thrust bearing
K
Temperature Trust Bearing Oil
Scale: 0-75 C
Normal: 35 C
Alarm: 55 C
Gas filled bulb, imbedded in thrust housing oil bath
L
Temperature Generator Lower Guide Bearing
Scale: 10-105 C
Normal: 50 C
Alarm: 70 C
Gas filled bulb, imbedded in the lower guide bearing
M
Temperature Turbine Guide Bearing
Scale: 0-105 C
Normal: 45 C
Alarm: 55 C
Gas filled bulb, imbedded in turbine guide bearing
N
Temperature Turbine Guide Bearing Oil Return
Scale: 10-105 C
Normal: 30 C
Alarm: 55 C
Gas filled bulb, imbedded in the turbine bearing oil sump
O
Sprial Case Pressure
Scale: 0-15 PSI
Normal: 8 PSI
Direct pressure line from spiral case
P
Headcover Pressure
Scale: 30-0-30 PSI
Normal: 8 PSI
Direct pressure line from head cover
Q
Turbine Guide Bearing Oil Pressure
Scale: 0-100 PSI
Normal: 22 PSI
Direct pressure line from turbine brg, oil pressure, line, wheel pit
R
Generator Cooling Water Pump Green/Red Light
S
Turbine Bearing Oil Pump AC/DC Green/Red Light
T
Generator Cooling Water Pump
On/Off Lever
U
Start Stop Control
Start/Stop Lever
V
Turbine Guide Bearing Oil Pump
On/Off Lever