Gas Equipment & Large Boiler 248 CMR 7.00 Flashcards

1
Q

Burner assemblies and all component parts shall be installed according to the ______.

A

manufacturers instructions and shall be properly and firmly secured in place to maintain correct alignment in normal use.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A low-water cutoff may be bypassed for what reason?

A

for blow down purposes only.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Linkage for controlling air and gas input rates are designed to ______.

A

reliably maintain correct air-gas ratio.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the primary function of a boiler limit control?

A

to prevent excessive steam pressure in a steam boiler or excessive temperature or pressure in a hot water boiler.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When shall combustion control be provided?

A

for burners with a firing rate of 2,500,000 BTUs per combustion chamber per hour and over

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

An electric ignition system shall ignite only…?

A

a pilot

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What shall an air shutter be capable of?

A

being readily adjustable to any desired setting and securely locked to prevent accidental change in setting.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

A pressure-operated safety shutoff valve shall close…?

A

upon failure of its operating pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How close to the entrance of a gas train must the gas shutoff be?

A

within 6 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

An electrically operated safety shut-off valve shall not _____

A

depend on electricity to shutoff the gas supply

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Natural and mechanical draft systems with continuously burning pilot(s) capable of igniting any gas flowing from the main burner shall, upon demand for heat, ______

A

prove all interlocks

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Natural draft systems with intermittent pilot or interrupted pilots, upon demand for heat shall ______

A

1.) prove all interlocks
2.) prove open for at least 90 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Gas main pressure regulators and gas pressure interlocks. Each burner assembly shall be equipped with a ___(A)___ main gas pressure regulator that will regulate within ___(B)___.

A

(A) listed
(B) plus or minus 10% of the operating pressure at all firing rates.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Except where zero governors are used in connection with air-gas mixers, all main gas pressure regulators shall be ______.

A

vented independently to a safe outdoor location

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Vent lines from main gas pressure regulators shall not be connected into a ___(A)___ with the bleed line from gas operated ___(B)___.

A

(A) common line
(B) diaphragm valves or from pressure relief valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What 3 materials can be used for vent lines?

A

1.) steel
2.) wrought iron pipe
3.) Corrugated stainless steel tubing (CSST)

17
Q

Vent lines shall extend no less than ______ above the roof surface.

A

18 inches

18
Q

vent lines shall be run to the outside using ___(A)___ and shall not be ___(B)___.

A

(A) shortest practical route
(B) trapped or installed in a manner that restricts air flow

19
Q

CSST vent lines shall transition to steel no less than ______

A

one foot inside the building

20
Q

Vent lines that terminate a building opening shall be located no less than ______

A

4 feet away from any building opening or air intake.

21
Q

Name 3 things for pilot testing.

A

1.) pilot burner shall be lighted and adjusted to manufacturers instructions
2.) pilots shall not deposit carbon
3.) when bleed pilots are used the discharge shall be in a fixed position

22
Q

complete written or printed instructions including wiring diagrams shall be ______.

A

supplied and made conveniently available or posted in permanent form near the equipment.