Gas Code Flashcards
A valve designed to activate when the fuel gas passing through it exceeds prescribed flow rate is a _____.
excess flow valve
An appliance that operates with a non-positive vent static pressure and with a vent gas temperature that is capable of causing excessive condensate production in the vent is a _____ appliance.
category II
Holes bored in a floor joist shall not exceed ____ their depth.
1/3
Bored holes shall not not be greater than ____ of the stud depth in non-load bearing walls where each bored stud is doubled.
60%
Gas appliances shall not be located in a ____ unless it meets one of the approved exceptions.
bathroom
A single wall mounted unvented natural gas room heater equipped with an oxygen depletion safety system maybe installed in a ____.
bathroom if it is 6,000 btu’s or less
Indoor combustion air for gas appliances using the standard method is sized based on ____ cubic feet per 1,000 Btu/h of the appliance input rating.
360
How many cubic feet of space would be required to use the standard method of combustion air for gas appliances if you had a space with 60,000 but fan assisted furnace, 34,000 btu natural draft water heater, and 28,000 btu gas dryer?
61,000 cu ft
(total btu / 1000) * 50
What would the maximum gas appliance btu input be for an open basement measuring 26’ x 52’ with 8’ ceilings, using the standard combustion method?
216,320 btu
(total cubic feet * 1000) / 50
When combining spaces on the same story to obtain the required combustion air for gas appliances, each opening shall be sized a minimum 1 sq inch for the total input rating of all gas appliances but not less than ____ sq inches.
100
The minimum dimension of air openings for combustion air for gas appliances is ____.
3 inches
When using two permanent openings to provide combustion air for gas appliances and communicating directly with the outdoors, each opening shall have a minimum free area of 1 sq inch for every ____ total input rating of all equipment in the enclosure.
4,000 btu
When installing all gas appliances ,combustion air is allowed to utilize one permanent opening commencing within 12” from the top of the enclosure. The opening must be a minimum 1 sq inch for every ____ total appliance input.
3,000 btu
When mechanical combustion air is provided for gas appliances, the combustion air shall be supplied from the outdoors at a rate not less than ____ cfm per 1,000 btu/h of total input rating of all appliances located within the space.
0.35
Where exhaust fans are installed, ____ air shall be provided to replace the exhausted air.
make up
Where the design free area of louvers and grilles are not known, it shall be assumed that wood louvers have ____% free area and metal louvers will have ____% free area.
25,75
Combustion air ducts for gas appliances shall not be ____ where terminating in an attic.
screened
Condensate waste and drain line size shall not be less then ____.
3/4” ID
Per the reduction table 308.2 2015 IFGC, when 0.5” insulation board is installed over 1” glass fiber or mineral wool batts, the required 12” clearance may be reduced to ____ for combustible items located above the vent connector for a gas water heater.
9”
A gas furnace required to have 12” clearance to combustibles for the side of the appliance can be installed within ____ if the wall is protected with 0.024” sheet metal that has ventilated air space.
4”
Gas central heating furnaces shall have the clearance from supply ducts within ____ of the furnace plenum but not less than that specified from the furnace plenum. No clearance is necessary beyond this point.
3 feet
The bonding jumper for CSST must be a minimum ____ AWG copper wire.
6
When adding an additional gas appliance to an existing gas system and the pipe system is found to have an inadequate capacity, the existing system shall be ____ as required or separate piping of adequate capacity shall be provided.
enlarged