Exam Prep IFGC, MMC, Manual D Flashcards

1
Q

A valve designed to activate when the fuel gas passing through it exceeds a prescribed flow is a ____.

A

excess flow valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When only indoor combustion air is used, a gas water heater located within a 10 foot by 10 foot room is required to have a minimum ____ cubic feet per 1,000 Btu/h.

A

50

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The approximate number of _____ threads are required to be cut for 3/4” metallic piping.

A

10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Plastic gas piping requires a ____ tracer wire be installed with a minimum ____ AWG.

A

yellow, 18

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Primer for plastic piping used in appliance venting must be what color?

A

contrasting color

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Vented gas decorative fireplaces shall be tested in accordance with ____.

A

ANSI Z21.50

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A commercial kitchen ____ hood is mounted directly to the face of the appliance.

A

eyebrow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

An evaporator cooling coil drain must be a minimum ____ in size.

A

3/4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Nail stations located within a specialty shop must have a source capture system capable of exhausting a minimum ____ cfm per person.

A

50

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A valve regulated lead acid battery producing manufacturer with a 10 foot by 10 foot room used to store batteries must have a minimum ____ cfm continuous ventilation.

A

100

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

A grease reservoir for a Type 1 hood shall ____.

A

Be located on the bottom of the horizontal duct

Have a depth of not less than 1”

Have a length and width not less than 12”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Energy recovery ventilation systems shall not be used in what systems.

A

commercial kitchen exhaust systems serving a Type I or Type II hood

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Fire sprinkler piping exposed within a plenum must have a flame spread of not greater then ____.

A

5 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The maximum horizontal length of a single wall connector used to vent an oil furnace shall be ____ percent of the height of the chimney or vent.

A

75

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Water heaters used for space heating and potable heating requires a mixing valve be installed to limit the maximum potable water temperature to ____ degrees F.

A

140

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When ____ pounds of a Group 1A type refrigerant is changed in a refrigeration system, the code official must be notified.

A

220

17
Q

Refrigeration piping joints located within an air duct must be tested to ____ percent of the higher of design pressure or pressure relief device.

A

150

18
Q

Hydronic piping using PEX-AL-PEX pressure pipe shall not have a solder joint occur within ____ of the pex pipe.

A

18”

19
Q

Fuel oil tank removal or abandonment must be done in accordance with ____.

A

International Fire Code

20
Q

Flammable gas or liquid heat transfer fluids for solar systems shall ____.

A

not be utilized

21
Q

What is the friction rate for a 120 foot duct system with a pressure drop of 0.4” wc?

A

.33

22
Q

What is the required furnace cfm with a heating load of 86,000 btu’s using an altitude correction factor of 2 and the supply air is 120 degrees and the room air is 70 degrees?

A

856

23
Q

What size round galvanized duct is required with a 0.1 friction rate at 700 cfm?

A

12”

24
Q

What is the equivalent length for a round pipe attached directly to a plenum in a return air system with a referenced velocity of 700 fpm at 0.08 IWC per 100 feet?

A

40 feet

25
Q

What is the equivalent length of a 30 degree elbow at 800 fpm and a 1.5 R/D ratio?

A

3.33

26
Q

How many cubic feet of space would be required to use the standard method of combustion air if you has a space with a 80,000 Btu fan assisted furnace, 40,000 Btu natural draft water heater, and a 32,000 Btu gas dryer?

A

7,600 cu ft

27
Q

What maximum total appliance btu input is allowed for an open basement measuring 30’ x 64’ with a 9’ ceiling to be able to use the standard combustion air method?

A

345,600 Btu

28
Q

A residential home has a total heating load of 62,000 Btu’s and designed with a furnace blower operating at 1240 cfm. How many cfm’s would be required for a bedroom with a heating load of 5,400 Btu’s?

A

108 cfm’s

Room CFM = (Blower CFM * Room Load) / Equipment sizing load

29
Q

A blower with an external static pressure of 0.54 IWC connected to a 60 foot duct includes a register and grille of 0.025 IWC each, a cooling coil of 0.16 IWC and a filter of 0.12 IWC. What is the total available static pressure remaining?

A

0.21 IWC

30
Q

A 75,000 Btu 95% furnace has a temp rise of 47 degrees. What is the required cfm with an altitude correction factor of 1?

A

1378

31
Q

HVAC cooling ducts exposed to the outdoors should have ____ installed to prevent condensation from forming on the exterior of the duct.

A

vapor retarder

32
Q

Mechanical equipment installed in a private garage must be installed in accordance with the ____.

A

2015 Michigan Residential Code

33
Q

The air temperature in non-metallic ducts shall not exceed ____ degrees F.

A

250

34
Q

Commercial kitchen grease ducts horizontal clean out must be a minimum ____ size.

A

12” x 12”

35
Q

In a commercial duct system, how many duct classifications exist?

A

14
7 positive
7 negative