Furnace Start Up Flashcards

1
Q

Furnace must be wired electrically and ground according to what? In the absence of that you should use?

A

Canadian electrical code (CEC), or CSA C22.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The blower motor should be checked for.

A

Shipping blocks or brackets removed, motor mount checked for tightness

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

3 ways to check for a gas leak

A

Test dial on gas meter
Commercial leak detector (soapy water solution)
Electronic leak detector

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How to check gas leak with test dial

A

Turn off gas to all appliances minus the one you’re working on, go to gas meter, locate test dial mark where dial is, wait ten minutes see if it moved.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What do electronic leak detectors detect

A

Detects the mercaptin.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

All venting systems are required to first follow

A

Appliance manufacturers installation instructions.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

All venting must match the what?

A

The category of furnace it is intended

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

All metal vent and vent connectors must be

A

ULC approved and adhere to b149 gas code

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Metal vent connector material must be installed so that there is no

A

Dips or sags with all joints fully inserted and locked together.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

All plastic vent must be certified to

A

ULC S636 and must be clearly marked.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Excessive air leakage could cause what

A

A shortage of warm air in certain rooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

On new construction it is good practice to?

A

Inspect entire heating ventilation and air conditioning.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What do you match the heat anticipator to?

A

The amperage of the 24 volt control circuit.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How to set a single stage Manifold pressure

A

Must turn off gas at the gas cock first and connect the manometer to the outlet pressure port on the gas valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Failure to set the air temp rise can result in?

A

Reduced furance life

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Where is the tempature rise readings taken from?

A

The supply air plenum but not in direct view of heat exchanger

17
Q

What must you do if temp rise is to low or to high

A

If to low decrease fan speed if to high increase fan speed.

18
Q

What are the speeds on a pcm used for

A

Low is continuous fan op
Medium is for heating mode
High is for cooling

19
Q

How to change speed in an ECM

A

Changing a series of small switches “dip sticks”

20
Q

How to test a high limit

A

Remove motor lead from heating terminal and placing it on a park terminal ( terminal that is never energized)

21
Q

In sequence of operation what is considered the pre purge and how long is it

A

1.Call for heat R&W closes
2.relay coil energized, closes contacts for inducer motor
3.pressure switch closes
Takes 15-45 seconds

22
Q

In the sequence of operation what steps are considered the trial for ignition.

A
  1. Relay coil energies, closes contacts for hsi
    2.relay coil energies, closes contact for gas valve
    3.burners ignite
    4.flame proves through rectification
    5.hsi de-energizes
23
Q

How long after the gas valve energized does it take for the main blower motor to start

A

30-45 seconds