Framing Flashcards
Fascia is not to be ___________ , ___________, or __________.
Damaged
Splintered
Waned
If gun nails are used to secure fascia what must happen?
All nail holes must be filled with no waffle/hammer marks.
What are the tolerances for exposed wood (beams, bucks, blocks, posts, sheathing, tails, corbels) regarding:
- Defects/delamination?
- Cracks?
- Knot holes?
- No tolerance, replace material
- Cracks not to exceed 6” and 3/32” in width
- Knot holes not to exceed 1/2”
How is fascia nailed at 2” X 6” tails?
3 nails with 2 showing (one is under the drip edge)
How is fascia nailed at 2” X 4” tails?
2 nails with one showing (one is under the drip edge)
What type of nails are used at fascia?
Non corrosive nails
Shiners at exposed areas are to be __________ and _________.
Removed
Patched
Fascia clips should be installed at all _________ and ________, except at the ________.
Corners
Joints
Ridge
Eave blocks and eave vents should be installed ________ , ________ and ________.
Plumb
Level
Square
Caulk gaps at eave blocks that exceed _______ of an inch.
1/8”
Do NOT caulk gaps at eave blocks that are less than _______ of an inch.
1/8”
Replace eave blocks with gaps that exceed ________ of an inch.
1/4”
Bows in walls are not to exceed ________ of an inch in _______ feet.
1/4”
8’
Bows in walls at cabinet locations are not to exceed _______ of an inch in _______ feet.
1/8”
8’