Flues Flashcards
Learn about different types flues and measurements according to regulations
What are the main regulations and standards applying to flues
Regulations 27,30,and 32 of the Gas saftey installation and use regulations.
BS5440 part 1:2008
Flueing and venting for gas Appliances of rated input should ot exceed
70KW
Hearth are constructed to a minimum thickness of what?
125mm
The concrete must extend fully into the fire recess and project at least?
And how many millimetres each side of the opening?
500mm in front of the jabs
150mm on each side of the opening.
A flue serving an open solid flue fire must contain a clear circular space of at least ?
175mm diameter
The need for lining in the chimney will depend upon ?
Type of Appliances, the input rating and the chimney height.
What do you check whether an existing chimney or flue conforms to standards which adversely affect the performance of the flue or result on blockage.
Check the route of the flue(through any loft space),conditions of the flue,whether there are any changes of direction,
Modern practice requires the flue to be constructed with one of the following
Brick or Masonry construction with clay lining to BS EN 1457
Brick or Masonry construction with concrete lining BS EN 1857
What is the size of the traditional brick chimney designed to be used with solid fuel stove and open fire and is adequate for gas Appliances ?
225×225 (9”x9”)
What are the three major categories of Appliances?
Room sealed ,open flued system, flueless.
In a vertex flue the combustion air is drawn from where?
With in the loft space
What is a forced draught?
This a driving force obtained from electric fan.
What is natural draught?
Using thermal convection ,Driving force in order to move gases along a chimney/flue system and expel them from terminal.
What are the 3 things that affect chimney and flue? performance
In natural draugh flue depends on?
# It's ability to create sufficient draught to propel the combustion gas. # Its ability to retain sufficient heat to maintain the water vapour to prevent condensation forming within the flue. # the capacity to handle the volume of the gases produced
Open flues system consists of four components?
Primary flue
Draught diverter
Secondary flue
Terminal