Field Inspection Guidlines Flashcards

1
Q

What is the minimum size for address numbers on a building?

A

4” x 2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Who may approve the need for a KEYBOX to be installed on a building?

A

Fire Chief

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the minimum size for a FDC sign?

A

8” high x 4” wide

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

The letters on hose and extinguisher cabinets must be how tall?

A

3”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When must a responsible resident live on the premises of an apartment or hotel?

A

Apartment- 16 or more units

Hotel- 20 or more units

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How often shall smoke detectors be tested?

A

6 months

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When are fire alarm systems required in apartments and hotels?

A

Apartments- 3 or more stories, 16 or more units

Hotels- 3 or more stories, 20 or more units

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fire alarm systems are tested how often?

A

Annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the minimum width for walkways, aisles, and aisle ways?

A

44”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Windows leading to fire escapes must be at least how wide when open?

A

29”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fire escape windows must be how high off the floor and the landing?

A

30”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Exit signs and directional signs must have block lettering how tall?

A

6”

With 3/4” stroke

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Stairwell signs shall be square and have a minimum dimension of what?

A

12 square inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fire extinguishers shall be serviced, inspected, and emptied how often?

A

Yearly or after each use

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Wires, rods, aerial or antenna mast can be attached to a roof structure but must have a clearance how high off the roof?

A

7 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Passageways on roofs must be provided every ___?

A

50 feet

17
Q

Passageways on roofs must be what size?

A

3’ wide x 7’ tall

18
Q

How many spare sprinkler heads are required for buildings with
1-300 heads
301-1000 heads
More than 1000 heads?

A

1 to 300- 6 heads
301 to 1000- 12 heads
>1000- 24 heads

19
Q

Extinguishers shall not have a gross weight over?

A

40 pounds

20
Q

When installed on a wall, the top of extinguishers shall not be more than how high off the ground?

A

5 feet

21
Q

The use or display of compressed gases shall not exceed how many days?

A

30

22
Q

Disconnect switches at auto fueling stations must be what distance from the dispensers?

A

15 to 100 feet

23
Q

No open flame is allowed within how many feet of auto fueling stations?

A

25 feet

24
Q

A division 5 permit is required for spray booths how big?

A

3 feet or more

25
Q

Liquified flammable gas shall not exceed how many gallons?

A

5.76 gallons

26
Q

Liquified flammable gas cylinders shall not be charged to more than what percent of its normal charging capacity?

A

50%

27
Q

The total amount of liquified flammable gas on a premises shall not exceed how many gallons?

A

60 gallons

28
Q

All exit doors shall be at least how big?

A

3 feet wide x 6’8” tall

29
Q

Exit doors shall be able to open so that the width of the exit is at least how wide?

A

32”