1
Q

What two entries to the steam generators does the Feedwater enter through?

A

Downcomer region

Economizer region

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Why is there a downcomer region and an economizer region into the steam generator?

A

Downcomer: to cools the water that is already doing the heat transfer
Economizer: to provide more heat transfer right before entering the cold leg (greater delta T = greater heat transfer)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

At what power levels are the downcomer valves providing flow?

A

Less than 15%: full open

Greater than 50%: 10% flow

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

At what power levels are the economizer valves providing flow?

A

15%-50%: full open

Greater than 50%: open in accordance to power level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Single Element Control of the Feedwater Control System

A

Measures Steam Generator Level

Used when Power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Three Element Control of the Feedwater Control System

A

Measures Steam Generator Level
measures and compares Steam Flow and Feedwater Flow
When power is > 16.5%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does feedwater flow rate maintain during a reactor trip override?

A

RCS temperature at 565 degrees F

Tracking when level