ESW Flashcards
What are the ESW pump auto starts with pump switch in auto?
- Low Header Pressure < 40# (only in Auto)
- SI- Load Shed
- Opposite unit SI
Will the ESW pump discharge valves automatically open on an auto ESW pump start?
Yes
Will the ESW pump discharge valves automatically open on a manual pump start?
Yes
Will the ESW discharge valve auto close on a trip?
No, they have no automatic closure function
What are the ESW pump trips?
- Load Shed
- Overload/Overcurrent
- Manual
What are the ESW pump power supplies?
- T11/21D East Pump
- T11/21A West Pump
What happens with the ESW to CCW HX outlet valves on a SI?
Go to pre-determined throttle position of approx 5000 gpm
can be re-positioned with Ctrl Switch after they reach preset position
What happens with the ESW to CTS HX outlet valves on a with a cts signal and on recirc sump?
After on recirc sump, Go to pre-determined throttle position of approx. 2400 gpm
(CTS Signal with ICM-305 or 306 Recric Sump Valves open)
Will opening the alternate ESW supply to the EDG cause the EDG to be inoperable?
Yes, because if you were to have a single failure, you have the potential to lose both trains of cooling
How is the alternate ESW supply to the EDG operated?
Manually
Which ESW header has the TDAFP emergency suction supply?
West Header
Which ESW header has the E MDAFP emergency suction supply?
East Header
Which ESW header has the W MDAFP emergency suction supply?
East Header
At what temp will the standby (even numbered) ESW room fan start?
90°F
When will the odd numbered ESW room fan start?
On the pump Start
Which units CA supplies both units ESW backwash strainer?
Unit 1
Describe the Auto actions of the ESW Pp Disch Strainer?
Automatic backwash of strainers:
- at 86.5” H2O DP
- every 24 hrs on timer
What is the max UHS Temp for Unit 1 and Unit 2 per TS 3.7.9?
86.9°F
At what pressure will the Backup Air Bottles start taking over at for the ESW strainer backwash valves?
42#
What are the ESW pump auto starts with pump switch in neutral?
- SI
- Load Shed
- Opposite unit SI
If you get a Unit 2 Train A only SI, what ESW pump(s) will get an auto start signal?
- U2 East ESW Pump
- U1 W ESW Pump
You have the ESW crossties open with both units E ESW pumps running and both W ESW pumps in standby. If your E ESW pump on Unit 1 trips out on instantaneous overcurrent, what will happen?
U2 W ESW pump will start on Low header pressure @ 40#
Is the auto start function of the ESW pump from a SI required for Operability?
YES!!! PER SR 3.7.8.3