What are the auto starts of the ESW pumps?
40#
SI.
Blackout sequence.
What happens to ESW on an SI?
All 4 pumps start and the CTS ESW outlet valves throttle to 2100gpm.
What are the loads on the ESW system?
Alt. supply to AFP. AFP room coolers. EDG air after coolers. EDG lube oil coolers. EDG jacket water coolers. CTS HX. CRAC. CCW HX.
What are the ESW pump power supplies
Unit 1 T11A West T11D East Unit 2 T21A West T21D East
If you had a CTS HX tube leak what would be leaking into what?
CTS would leak into ESW.
If you had a CCW HX leak what would be leaking into what?
CCW would leak into ESW.
If you had a CRAC HX leak what would leak into what?
Chill water would leak into ESW.
What is the alternate water supplies to ESW?
WMO-17 or 27
When do the CTS HX ESW outlet valves open?
Only if you have a CTS signal and ICM-305 or ICM-306 are open.
What would happen if you were manually switching ESW discharge strainers and you only operated one gate valve at a time?
You would isolate ESW from that pump.
What happens to ESW if you loose Unit 2 control air?
Nothing all control air is supplied from Unit 1
What would happen to ESW if you lost Unit 1 control air?
When header pressure lowered to 42# the backup air bottles would supply air to Backwash valves.