ESFAS Flashcards
Discuss the basis for ESFAS.
Limits core damage and minimize offsite releases during design bases events by the actuation of systems designed to provide core cooling, establish containment isolation, and protect containment integrity
List the inputs to ESFAS.
- RWT level (4)
- Pzr pressure (4)
- Ctmt pressure (4)
- Ctmt radiation (4)
- SG A pressure (4)
- SG B pressure (4)
Discuss what is contained by the four ESFAS Measurement Channels (MA, MB, MC, MD).
- Trip bistables.
- Isolation modules.
- Auto and manual test circuits
Discuss what the two Actuation Trains (SA & SB) each contain.
- Actuation modules with logic matrix.
- Isolation modules.
- Auto and manual test circuits.
- Output relays.
- A separate enclosure for “C” component actuation circuitry.
- Each train has parallel output relays for “C” CCW, ICW, and Charging pump.
Discuss EDFAS interfaces.
RPS Instrumentation inputs that is shared.
a) Pressurizer pressure
b) Containment pressure
c) S/G pressure A
d) S/G pressure B.
* Radiation Monitoring System shares CIS monitors.
* ATWS/DSS shares PZR Pressure
Discuss the ESFAS Measurement Cabinets.
- Four measurement cabinets (MA, MB, MC, MD) are located behind RTGB 106 [206] separated by metal barriers.
Channel MA: ‘A’ Train Power: (MA instrument bus)
Channel MC: ‘A’ Train Power: (MC instrument bus)
Channel MB: ‘B’ Train Power: (MB instrument bus)
Channel MD: ‘B’ Train Power: (MD instrument bus) - ATI located in {MA Cabinet on Unit 1} and [SA Actuation Train on Unit 2]
If an ‘A’ MSIS signal is generated, what indications will be present?
- The ‘A’ MSIS handswitch “RED” light will illuminate. The ‘B’ MSIS handswitch “RED” light will NOT illuminate, but the ‘B’ train MSIS components will reposition.
- No matter which train gets the actuation signal, interposing relays ensure actuation of both trains of components
How are ESFAS bistables tripped?
UNLIKE RPS, WE DO NOT PULL THE TRIP BISTABLES FOR ESFAS
WE ONLY PULL THE ISOLATION MODULES*
Discuss Auto Test Insertion Module (ATI).
- {Located on Panel MA} [Located on Panel SA]
- Continuously monitors the ESFAS operability by performing on-line testing of the ESFAS circuitry.
- Accomplishes by continuous “pulsing” of actuation circuitry:
- Under-pulse: A 5% under setpoint signal to check for no actuation.
- Over-pulse: A 5% over setpoint pulse to check for actuation
- The ATI inserts signals into 2/4 bistable actuation flowpaths:
a) It inserts an under pulse; and then monitors that the bistable DOES NOT trip
b) It inserts an an over pulse; and then monitors that the bistable DOES trip - Why doesn’t the ATI module signal generate an ESFAS actuation signal?
The ATI test signals only trip the bistables/actuation modules for 2 milli-seconds
a) Output relays need signal present for ~ 30 milli-seconds to actuate
b) Signal resets before output relays can “actuate” on the signal
c) No actual component actuations occur
Discuss ATI Test LEDs.
- Not illuminated – Means bistable tripped on under-pulse.
- “Constantly” illuminated or Illuminated for a longer time – means failure to trip on over-pulse.
- Either results in Annunciator alarm and indicator lights on ATI panel.
- Test Panel is for I&C to periodically test and verify the B/S trip setpoints
Discuss ESFAS Actuation Cabinets.
- Two trains (SA, SB) with 2 cabinets per train
- Each cabinet uses auctioneered power supplies to ensure the loss of one power supply will not cause an actuation
- Cabinet SA: Dual Powered from MA & MC instrument buses
- Cabinet SB: Dual Powered from MB & MD instrument buses
- Actuation modules:
a) Input to the actuation module is isolation module output
b) Develops the 2/4 actuation logic
c) Logic signal development from B/S to Actuation Logic is “electronically” generated and passed (i.e., no relays)
Discuss ESFAS Signal Flowpath.
Instrument Channels
2/4 Logic Matrix
Actuation Module
Output Relays
Equipment Operation
Discuss ESFAS Block Modules.
- Output is signal to actuation relays.
- Applicable to SIAS and MSIS only.
- Requires 3/4 logic to block – meaning you must have 3/4 channels at the block setpoints
Discuss ESFAS Blocking.
- Requires key switch manipulation to block the applicable ESFAS signal
- Amber light lit above Block key switch
- Annunciator should light for Block permissive
- When switch is taken to block, then red block light should come on and amber light will go out
- Block annunciator will also come in.
Discuss ESFAS Manual Actuation/Reset Pushbuttons.
- It is a two function switch which will allow actuation or resetting of SIAS or CIAS
- Signal actuation requires two actions. First a pushbutton must be held depressed and then a control switch is taken to “Actuate”
- For reset, positioning of the switch to the “Reset” position is all that is required. (Assuming no signal is present, or signal has been blocked)
- To reset an ESFAS signal: You must either block the actuation signal, or not have the signal present.
- Can’t block containment pressure into SIAS [MSIS]
Discuss EOP-99 additional reset criteria.
SIAS
Unit 1
CTMT Pressure < 4 psig and not rising
Low RCS pressure input met or blocked
Unit 2
CTMT pressure < 3.4 psig and not rising
Low RCS pressure input met or blocked
CIAS
Unit 1
CTMT Pressure < 4 psig and not rising
CTMT Radiation is < 8 REM and not rising
SIAS not actuated or is reset
Unit 2
CTMT pressure < 3.4 psig and not rising
CTMT Radiation is < 8 REM and not rising
SIAS not actuated or is reset
MSIS
Unit 1
Low SG Pressure input met or blocked
Unit 2
Low SG Pressure input met or blocked
CTMT pressure < 3.4 psig and not rising
CSAS
Unit 1
No extra criteria
Unit 2
No extra criteria