EPRI ch 4 Flashcards
According to load/frequency relationship, a 1 percent change in frequency will lead to what approximate magnitude load change in a 10,000 MW system?
a) 500 MW
b) 1,000 MW
c) 200 MW
d) 50 MW
c) 200 MW
A governor with zero speed droop is also known as a _______ governor
a) flat frequency
b) transient loop
c) B-loaded
d) isochronous
d) isochronous
The governor response rate of Steam turbines is better than a Hydro turbine?
True or False
False
Control area frequency bias is:
a) control area frequency response characteristic
b) natural response of the control area
c) the AGC system bias value
d) all above
d) all above
Which on of the following is not a control mode of AGC operation?
a) Flat Tie-Line Control
b) Isochronous
c) Flat Frequency Control
d) Tie-Line Bias Control
b) Isochronous
Which stage of a generator’s response to a system disturbance is power flow supported primarily by the exciter system?
a) Governor response
b) AGC stage
c) Electromagnetic charge stage
d) Inertia stage
c) Electromagnetic charge stage
After 2 HRs that the interconnection is operated with a frequency of 60.02 HZ, how much time error will accumulate?
a) 2.0 secs
b) 2.4 secs
c) 1.0 secs
d) 1.2 secs
b) 2.4 secs
If Bias is -150MW, and frequency falls .05HZ, how many MW does control area provide?
a) -75 MW
b) 75 MW
c) -150 MW
d) 150 MW
b) 75 MW
An isochronous governor has what speed droop?
a) 5%
b) 0%
c) 10%
d) 8%
b) 0%
What is most susceptible to damage from abnormal frequency operation?
a) A transformer of 300MVA or greater
b) low pressure steam turbine blades
c) synchronous motor
d) induction motor
b) low pressure steam turbine blades
The North American power system is divided into areas called interconnections
T or F?
True
Time Error
60 HZ = no time error
under-generation = faster time error
over-generation = slower time error
T or F?
False
All load can be divided into two general types; non-motor load and motor load
T or F
True
Lowering the voltage will increase a motor’s speed?
T or F
False
Electric generators use what to control shaft speed?
governor control systems