Emergency Operating Situations Flashcards
1
Q
What do you do on a boiler feedwater trip
A
Get field op to utilities quickly
Put both boiler FICs to manual 0
Put back up feedpump jap switch to stand by
Start pump from the field
Cascade the FICs when the level PV is close to SP
Trouble shoot offline pump
2
Q
Aux trip
A
- Inform field ops to relight to boiler
- Supper heat to 440c
- Slow PIC-4010 to back steam system up and to get plant rate to 24m
- Set FIC-6060 and FIC-6061 to manual 18/6
- Get FIC-6063 to manual
- Once boiler is running field will transfer control back to you
- Get super heat back to normal and get rates back up
3
Q
Super Heater trip
A
- Tell field ops the super heater tripped
- Put FIC-6041 on manual 0
- Once pilots are in open FIC6041 to light mains
- Fire manually until temp is stable
4
Q
Loss of C-402
A
-Back out of loop to stop snuffing R-501 with high percenage of NH3