EARTHING ARRANGEMENTS AND PROTECTIVE CONDUCTORS Flashcards

1
Q

any question on sizing of bonding conductors -

bonding conductors link extraneous conductive parts to the M.E.T

A

sizing of bonding conductors is determined by the sizes of live conductors going into it.
and should refer to table 54.8 on pg 203.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Main Earthing Terminal. pg196

every installation needs an m.e.t and is the hub of the earths in the property.

A

its where all cpc’s connect to. all bonding conductors connect to. most of the time is a external metal terminal next to the consumers unit.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

protective conductor sizing.
like a seatbelt , it does nothing until theres a fault. an extortionate amount of current goes into a conductor, will it withstand that much current until the protective device starts to operate.

A

is all down to how much fault Current is present when there’s a fault.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

s = √I squared X t divided by K.

A

s - the calculated size of protective conductor
I = the fault current
t - time taken for device to operate (0.1-0.4s)
k - a limiting factor for different cables and instalations

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

questions about what can be used an an protective conductor

A

top of pg 199. cpcs need to be accessible for inspection , testing and maintenance and no switching device should be on a protective conductor except electronic equiptment.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

when OCPD are used for fault protection the protective conducter should be..

A

installed in the same wiring system as live conductors or its immediate vicinity.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly