Differential Relays Flashcards

1
Q

differential relay schemes and equipment they protect

A
bus
transformer
breaker
shunt caps
reactors
series caps
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

list the types of relays for differential relay schemes for the bus

A

EM : CO-9, CO-11, IAC, PJC
SS : INX-5
MP : REB-670, RED-521, RED-531, BE1-851, BE1-951, SEL-487B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

list the types of relays for differential relay schemes for transformer/ reactors

A

EM : HU-1, HU-4, BDD, IJD,
SS : KBCH, MBCH
MP : RET-670, SEL-387, SEL-487

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

list the types if relays for differential relay schemes for shunt caps

A

MP : SEL-187V, SEL-287V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

list the types of relays for differential relay schemes for breakers

A

MP : SEL-587, SEL-787

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Slope

A
  • a setting on the differential relay that allows a certain amount of current in the operating coil before it will send a trip output.
  • is a percentage set between 20-40%
  • Relays with a slope setting are referred to as Percentage Differential
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

CT Mismatch

A

-In order for differential relay to normally see balanced secondary current in and out of the transformer Zone of Protection, CT ratios are selected so that the secondary current of both CTs are normal equal.
Example: for a 2:1 transformer, CTs should be selected that have a turns ratio of 1000:5 on the high side and 2000:5 on the low side
-CT Mismatch occurs when exact turns ratios can’t be used, or tap changer effects then transformer turns ratio

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

CT Saturation

A
  • A saturated CT will produce inaccurate secondary current
  • This will cause differential relays to see a imbalance when there isn’t one
  • CTs are designed to not saturate until 20 times their normal current rating
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Magnetizing Inrush

A
  • When a deenergized transformer is first energized there is an immediate inrush of magentizing current which may be many times greater then full load current
  • This current flows only long enough to establish the magnetic field of the transformer
  • During this time the differential relay will see current entering the Zone of Protection but not leaving it, this can cause a trip output
  • Consists mainly of reactive power
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Percentage Differential

A
  • Is used to compensate for mismatched CTs, losses within the Zone of Protection, and differing CT lead losses
  • Is achieved by having 3 windings (2 restraint in series and 1 operating in parallel) in the relay with different numbers of turns.
  • The restraint coils have 5 turns each and the operating coil has 40, this requires much more current flow in the operating coil in order to output a trip
  • The number of turns in each coil establishes the slope
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Harmonic Restraint

A
  • Uses tuned circuits to disable the operating coil of the differential relay during transformer energization
  • One tuned circuit blocks harmonics is used with the operating coil
  • Another tuned circuit blocks fundamental frequency is used with the restraint coil
  • Because magnetizing inrush consists mainly of reactive power there is al large amount of harmonic frequency
  • This allows most of the inrush to pass through restraint coil, preventing the disc from turning and initiating a trip
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Under Load Tap Change

A
  • Some transformers have the ability to change the voltage of the transformer by remotely adjust the turns ratio
  • Because the turns ratio is changed an imbalance can be seen by the differential relays
  • Using a percentage differential relay will help prevent false trip outputs due to ULTCs
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Define the term “Overlapping Protection” for differential relays.

A
  • Ensures that all equipment is protected.
  • Achieved by overlapping the Zones of Protection of adjacent Diff relays.
  • The Zone of Protection for a relay is set by the location of the CTs the relay gets inputs from.
  • Considered ideal protection.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Basic concept of a differential relay

A

What goes into the Zone of Protection must come out

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is a Zone of Protection for a differential relay

A

Protects specific bus and equipment

Boundaries defined by the CTs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

IEEE number for differential relays

A

87

17
Q

What is typically used as backup protection for a transformer differential scheme

A

Phase and neutral overcurrent relays
Tertiary ground detector
Sudden pressure relays

18
Q

When shall Bus Differential relays be cut out per WS-4-1

A
  • Before relay maintenance is performed

- Before a CT source in the differential relay scheme is bypassed or removed, that could adversely affect the relay

19
Q

When are Transformer differential relays cutout per WS-4-1

A
  • Before relay maintenance is performed.

- Before a CT source in the differential relay scheme is bypassed or removed, that could adversely affect the relay.

20
Q

When shall shunt reactor differential relays be cut out per WS-4-1

A

-Before relay maintenance is performed

21
Q

When she’ll shunt capacitor differential relays be cut out per WS-4-1

A
  • Before relay maintenance is performed
  • Anytime a capacitor section is in service and a potential source is to be interrupted to the voltage differential relay
22
Q

What makes differential relaying the most selective relaying principal

A

The selectivity of this type of relay resides largely in the connections of the current Transformers and their locations

23
Q

How does a line differential relay scheme work in basic

A
  • Relays compare the difference in current on the line via microprocessor relays and Communications paths.
  • Measures the instantaneous value (charge) of each phase and residual current as often as once every 1/2 millisecond, the local and remote charges are compared checking polarity into account. If the net charge differs from zero by more than a small threshold level an internal fault is declared and the power circuit breaker trip signals are sent.
  • Differentials are not commonly used on transmission lines though some exist, most for shorter lions like between a Powerhouse and substation.
24
Q

What are some best practices when restoring from maintenance of a SEL relay and why.

A

Always press the reset button on an SEL relay following maintenance.
-this resets possible trip outputs that were not indicated on the faceplate LEDs preventing false tripping

25
Q

What is an inherent relay trap when disabling and INX-5 differential relay

A

These realize trip to both the LOR and each PCB