Master element
The initiating device to place an equipment in or out of operation
Time delay starting or closing relay
Gives a desired amount of delay between operations in an automatic sequence
Master contactor or relay
Generally controlled by device no. 1, to place an equipment into operation under the desired conditions and to take it out of operations under other or abnormal conditions
Stopping device
Primary function is to place and hold an equipment out of operation
Starting circuit breaker, contactor or switch
Principal function is to connect a machine to its source of starting voltage
Anode circuit breaker
Used in the anode circuits of a power rectifier primarily to interrupt the rectifier circuit on arc back
Control power switch
Manually operated switch or circuit breaker used for the express purpose of connecting and disconnecting the source of control power to and from the control bus or equipment
Reversing device
Used to reverse the shunt field connections of a synchronous converter during the starting sequence or for other special reversing functions
Unit sequence switch
Used to change the sequence of placing units in and out of service in multiple unit equipment