definitions - ballast 28 Flashcards
are a measure of the approximate average yearly temperature difference between the outside and the inside in a particular location.
degree days
is based on the transfer of heat during the liquefaction and evaporation of a refrigerant.
compressive refrigeration
produces chilled water and is accomplished by the loss of heat when water evaporates. This evaporation is produced in a closed system by a salt solution that draws water vapor from the evaporator.
absorption refrigeration
It is the cooling effect obtained when 1 ton of 32°F ice melts to water at 32°F in 24 hours. This is equivalent to 12,000 Btu/hr (3516 W).
ton of refrigeration
This is a self-contained unit that passes nonducted air, which is to be cooled, over the evaporator and back into the room.
direct expansion, or DX, system (DX), also known as an incremental unit.
cool or heat spaces by conditioned air alone. Heat is transported to the space with supply and return air ducts.
all air systems
This system provides two parallel ducts, one with hot air and one with cool air. These two streams of air are joined in a mixing box in proportions to suit the temperature require- ments of the conditioned space. A thermostat controls pneumatic valves in the mixing box to create the proper mixture
dual duct (high velocity system)
With this system, air is heated or cooled as required in a central plant and distributed to the building at a constant temperature through a single duct. At each zone, a thermo- stat controls a damper that varies the volume of conditioned air entering the space to respond to the user’s needs.
Variable air volume system VAV
takes return air and fresh outdoor air and cools and dehumidifies the mixture, which is then distributed in a constant volume at low temperature throughout the building. At or near the spaces to be conditioned, the air is reheated as required by the cooling load of the space.
Reheat (constantvolume) system
uses a fan coil unit in each conditioned space. The fan coils are connected to one or two water circuits. Ventilation is provided with openings through the wall where the fan coil unit is located, from interior zone air heating, or by simple infiltration.
all water system
rely on a central air system to provide humidity control and ventilation air to conditioned spaces. However, the majority of the heating and cooling is pro- vided by fan coil units in each space
air water systems
In air ducts, there is a loss of pressure due to the friction of the air moving through the ducts, fittings, registers, and other components. The pressure required to overcome this friction loss is called the
static head
reuses outdoor air when it is cool enough to mix with recirculated indoor air. This reduces the energy required for refrigeration and is useful when the outdoor air temperature is about 60°F
economizer cycle
heats water by passing hot gases directly through the water.
direct contact water heater
recovers the sensible and latent heat from the high heat of exhaust flue gases that would nor- mally be discharged to the atmosphere.
recuperative gas boiler