control building interlocks Flashcards

1
Q

ah-e-19 has to be running to start which? that does what? (normal ventilation)

A

to start 17, which auto starts 95

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

ah-e-18 starts, what happens? (emergency ventillation)

A

auto starts 19, and 95

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

ah-e-14 must be running to start:
and that needs to be running to start which?

A

20, and 20 needs to be running to start 21/26

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

ah-e-19 trips, causes what? (normal ventillation)

A

causes 17 to trip, causes 95 to trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

ah-e-18 trips, causes

A

causes 19 to trip, and 95 to trip (emergency?)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

ah-e-14 trips, causes

A

20 to trip, causes 21/26 to trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

rm-a-1gas high trips what?

A

AH-E-17A/B, 20A/B, 21, 26, 93A/B, 94A/B and 95A/B Trip​

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

RM-a-1 Gas high, what fan stays running?

A

AH-E-19

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

RM-A-1 Gas high, which dampers close?

A

AH-D-28/617

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

on RM-A-1 gas high Operator starts which fans and per which procedure?

A

Operator starts AH-E-18/90/91 fans per OP-TM-826-901

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

RM-A-1 Gas high, all together now (trip, run, dampers close, starts)

A

AH-E-17A/B, 20A/B, 21, 26, 93A/B, 94A/B and 95A/B Trip​

AH-E-19 stays running​

AH-D-28/617 Close​

Operator starts AH-E-18/90/91 fans per OP-TM-826-901

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

AIT protective device, what trips?

A

AH-E-20A/B, 21, 26, 93A/B and 94A/B Trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

AIT protective device, which stay running

A

AH-E-17/19/95 stay running

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

AIT protective device, which dampers close?

A

AH-D-4/5/28/617 close​

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

4# ESAS, which fans trip on both sides of ES, which fans do they cause to trip? (8 total tripped at end)

A

AH-E-20A/B Trip on both sides of ES​

Causes AH-E-21 and 26 to trip​

AH-E-93A/B Trip on both sides of ES​

Causes AH-E-94A/B to Trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

4# ESAS, which dampers close on both sides of ES? which fans stay running, and operator re-aligns for emergency recirc like RM-A-1 actions per what?

A

AH-D-28/617 Close on both sides of ES​

AH-E-17/19/95 stay running ​

Operator re-aligns for emergency recirc like RM-A-1 actions per OP-TM-826-901

17
Q

4# ESAS all together now

A

AH-E-20A/B Trip on both sides of ES​

Causes AH-E-21 and 26 to trip​

AH-E-93A/B Trip on both sides of ES​

Causes AH-E-94A/B to Trip​

AH-D-28/617 Close on both sides of ES​

AH-E-17/19/95 stay running ​

Operator re-aligns for emergency recirc like RM-A-1 actions per OP-TM-826-901

18
Q

Fans high temp cutout is what? heaters have 2 high temp cutouts, one that auto reset and one needing manual reset, what are those setpoints?

A

125F
160F auto resets and 190F need manual

19
Q

Tech specs
1 train inoperable, how long?
2 trains inoperable, how long to do what or be in CSD in how long?

A

1 train inop =7 days
both = 2 hours to stop fuel handling, csd in 48 hours