Conductor Material & Sizes Flashcards

1
Q

Which condition is NMD90 suitable for?
A) Wet locations
B) As a consumer’s service conductor
C) Direct burial
D) Branch circuits

A

D)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the primary function of a sheath?

A

To provide a hermetic seal.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the maximum allowable conductor insulation temperature of T90 Nylon if it is exposed to oil?

A

60° C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If a conductor is not marked with a low temperature rating, what is the recommended minimum installation and handling temperature?

A

-10° C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the minimum size of equipment wire rate at 300 V that can be used, if it not for wiring a luminaire?

A

No. 26 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What temperature column of Table 2 would be used to size the NMD90 conductors for a range in a dwelling unit, if it is connected to a 40 A circuit breaker rated at 75° C at one end, and a 14-50R receptacle with no marked temperature rating at the other?

A

60° C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the minimum size of RW90 conductor that can be used for a non-continuous 50 A load, if the conduit the conductors are in contains eight current carrying conductors? Equipment and terminations are rated at 75° C.

A

No, 4 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the minimum size of TW75 conductors that can be used for a 120 A non-continuous load, if the conductors are run through an area with an ambient temperature of 45° C?

A

No. 1/0 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the minimum size of SJOW flexible cord that can be used to feed a 13 A non-continuous load of the cable they are in contains five current carrying conductors?

A

No. 12 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the percent demand factor that can be applied to a neutral conductor, where the ampacity is greater that 200 A?

A

70%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly