Two basic categories of air distribution?
Constant Air Volume (CAV) / Variable Air Volume (VAV)
List different CAV systems
- Unitary/stand alone
- Single zone
- Terminal reheat
- Face and bypass
- Multi zone
- Dual duct
- Under floor air distribution (UFAD)
- Make up air
In a single zone system, where is the air conditioned?
In the air handling unit
What controls the preheat coil in terminal reheat?
All heating, cooling, fresh air introduction and filtering is controlled as a function of the AHU
What controls the reheat terminal in terminal reheat system?
A zone valve which is controlled by a zone thermostat that modulates the flow of heated water or steam through the reheat coil
What is the expected temperature of a cooling/heating terminal?
100-190 for heating and 40-60 for cooling
What is the primary consideration for face bypass with a DX coil?
Evaporator capacity control must be used
What type of damper blades are used in face bypass for more accurate control?
Opposed blades
In a cooling only, face bypass system, what position will the dampers be in if zone temperature is below setpoint?
Closed so that air bypasses the cooling coil
What controls the mixing air damper actuator in a multi zone system?
Independent zone thermostats for each zone control independent mixing damper actuators in the AHU
What controls hot and cold deck temperatures in a multi zone system?
Function of the AHU
Typical hot and cold deck temperatures in a multi zone system?
90 and 55
What is bucking?
Inefficient state of heating and cooling at the same time
Typical neutral deck summer temperature?
Heats the zones using 75-80 air
How many actuators does a CAV dual duct system have?
Single actuator controlling mixing dampers
What does UFAD stand for?
Under floor air distribution
What temperature does a CAV MUA supply?
Constant volume near room temperature
When can you use DFMUA for sleeping applications?
Never
What are IFMUA heat exchangers made of?
Stainless steel in series
What is the supply air temperature of a VAV system?
AHU provides a variable air volume at a constant 55 supply
How do VAV systems control building static pressure?
Return air volume dampers or by maintaining positive building pressure between ventilation air
What happens to the bypass air from VAV bypass terminal?
Returns unused supply air to the AHU through the return air system
How many dampers does a dual duct VAV mixing terminal have?
Two
What are the advantages of a true VAV system?
Energy efficient and good humidity control
3 components of a DCV system?
- BAS systems with baseline schedules
- Motion sensors
- CO2 exhaust sensors
4 methods to accomplish VAV
- Modulate the outdoor air volume using a damper
- Variable speed supply motor
- variable speed supply motor with modulating profile plate
- Complex system of outdoor air and return air dampers
List the 4 types of systems
- All air
- all water
- Air and water
- DIrect
What basic type of system is a terminal reheat system?
All air