Commerial HVAC Drawing Flashcards
What temperature does a CAV NUA supply?
Near room tempurature
What is a typical neutral deck summer terminal?
75*F to 80*F
What type of climate would you install a Single Duct VAV System?
A place where it is continuously warm climate.
The RTU doesn’t have a heat exchanger.
Baseboard heaters of heat coils in VAV proved heat to room.
What type of damper blades are used in FB (face bypass) systems to provide more accurate zone comfort conditions?
Opposed Blade Dampers
How many actuators does a CAV dual duct terminal have?
Single Actuator controling S/A temperature from a zone thermostat.
What is a :
Recirculating Direct Fired Make-Up Air Unit?
A Direct Fired MUA that can utilize return air.
What percentages do Variable Air Volume systems save on electric and fuel consumption?
20% to 30%
What is the prime consideration when using FB (face bypass) with a DX coil?
You must have a Evaporator Capacity Control
Single Duct VAV systems adjust the volume of the air entering the space.
True or False
True
How do AHU (air handling units) provide the proper supply air temperature?
- Hot or Chilled water Coils
- DX (refigerant)
- Steam Coils
- Heat Recovery
- Heating Elements
- Steam Grids
- Economizer functions
What are MUA (make-up air units) used for?
To replace the air that is expelled by a building’s exhaust system, maintaining the proper balance between inside and outside air pressure.
Whatv are IFMUA heat exchangers made of?
Stainless Steel
What is the coldest expected coil temperature of an induction cooling terminal?
Coil temperatures cooler than 50*F often cause condensation problems.
What sizes of pipe with rtaes of flow will produce 1 Ton of Cooling?
- 5/8” OD pipe (2.4gpm @ 6 fps)
- 8” Spiral (400 cpm @ 1200 fpm)
- 5” Spiral (400 cfm @ 3000 fpm)
List 4 CAV HVAC systems.
- Unitary or Stand Alone
- Single Zone
- Multi Zone
- Under Floor
How does a bypass VAV system vary the volume of air being delivered to a space?
The bypass varies the air volume in the spaces by cycling unneeded conditioned air back to the central unit without allowing it to pass through the spaces.
List 4 types of control agents used to affect temperature changes in HVAC systems?
- All Air
- All Water
- Air and Water
- Direct Refigerant (DX)
List the 2 different types of fan powered terminal units.
- Constant volume (series flow)
- Variable volume (parallel flow)
Why is control of a VAV system critical?
Without proper and rapid flow rate control , either the systems’s ductwork or sealing can be damaged by over pressurization.
What will happen in some HVAC systems that are zoned if no bypass damperis installed?
Too much air may try to go to this zone and create excessive noise and uncomfortable drafts and can cause damage to the HVAC unit.
What are the 2 basic categories of air distribution systems ?
- CAV - constant Air Volume System
- VAV - Variable Air Volume System
Explain the difference between a regular VAV systems and a True VAV system.
The regular VAV system does not change the speed of the fans like a true VAV system does.
The regular VAV system uses dampers to throttle or bypass the air to control its quantity.
List the 4 types of VAV systems.
- Single Duct
- Dual Duct
- Bypass
- True VAV
What is the issue with a CAV Mixed Air System?
It is not proficient at controlling the humidity
What temperature is air delivered at in a CVS single zone reheat system?
55*F (13*C)
What devices controls the motorized dampers?
The CENTRAL CONTROL PANEL is a computer that controls the function of all dampers that are connected to it.
What controls the mixing damper actuator in a multi-zone system?
An indendant zone theramostat.
List the five (5) advantages to using VAV diffusers.
- Individual space control; and comfort
- Control of the required air volume for each zone
- ease of installation and relocation
- flexibity for future requirements
- Ease to maintenance
What does the acronym VAV stand for?
Variable Air Volume
What is the supply air temperature of a VAV system?
55*F
What is the acronym UFAD?
Under Floor Air Distrabution
A True VAV sytem varies the __ ____ to control the temperature in a space.
air volume
How do VAV systems control building static pressure?
Use a variable CFM supply fan.
Define : DUAL DUCT NON-MIXING
Dual duct VAV terminals use 2 duct inlets :
1 supplying warm tempered air while the other is supplying cool air. There is no mixing of these airstreams, just a simple opening or closing of either damper depending on whether the thermostat is calling for heating or cooling
What controls the Reheat Terminal in the Terminal Reheat System?
A zone thermostat that controls a zone valve that modulates the flow of heated water or steam.
Describe the difference between a multizone and a three deck multizone system.
The three-deck system is similar to the dual duct and multi-zone systems, except that there is an additional (third) air stream that is neither heated nor cooled.
What are 2 types of DUCT Terminations ?
- Dual Duct Mixing
- Dual Duct NON-Mixing
With CAV Multi-zone sytems Air Handing Unit, what are the typical hot and cold deck temperature in a multi-zone system?
90*F to 55*F
What controls the preheat coil in the Terminal Reheat System?
Zone Independant Thermostat
List 2 types of MUA (make up air) units.
- Direct Fire
- Indirect Fire
What controls hot and cold deck temperature in a multi-zone system ?
The RTU.
approx. 90*F to 55*F
The bypass VAV system uses the ______ or _______ of a ______ ______ to control the space temperature.
opening or closing of a volume damper
List the 2 deffierent types of bypass dampers
- Barometric Damper
- Motorized Damper
A dual duct system maintains the temperature in the space by doing what?
Increasing or decreasing the quantity (volume) of heated or colled air.
How does a multi-zone unit control the temperature of the air that is being distributed through the ducts?
The mixing of the airstream is done at the central air unit with the use of a set of interlocked motorized dampers.
When is it acceptable to use a DFMUA to DFMUA to areas with sleeping accommodation?
NEVER
List 3 components of a DCV (demand control Ventilation) control System.
- BAS systems with baseline schedules
- Motion sensors to confirm occupancy
- CO2 Exhaust sensors to monitor IAQ (indoor air quality)
What is the air temperature that is delivered from the central air handling unit in a CVS (constan volume system)?
55*F (13*C)
What is an advantages of a True VAV System?
Excellent Humdity Control
On what princple does an induction terminal unit work?
The induction terminal unit uses primary air supply flowing through a nozzle or group of nozzles to induce room air flow through the terminal heating and cooling coils.
List the 3 applications of direct fired makeup air systems.
- Make Up heating / cooling
- Space heating
- Space pressure control
How many actuators does a DDVAV Mixing Terminal have?
2 Actuators