All fittings that are not clearly identifiable should be
Rejected
All markings shall be legible and must have the following requirements
Manufacturers name or trademark
Service designation
Material designation
Steam boiler fittings are defined as
Devices directly attached to the pressure part of the boiler
Three methods of testing the accuracy of a pressure gauge is
Test gauge comparison
Dead-weight tester
Hydraulic comparator
What is test gauge comparison
Attaching an accurate gauge to a boiler while in operation to compare the accurate gauge with the gauge being tested
An essential fitting between the boiler and the steam pressure gauge is
A siphon
A steam pressure gauge may be graduated in
Kilo pascals
The scales on a pressure gauge for a steam heating boiler shall be graduated between one of the following
200 to 414 Kpa
An inspectors test connection is
No mandatory on lp boilers
When installing a siphon it
Should be first filled with water
When using a dead weight tester, the effect of friction
Is reduced by rotating the platform
The working medium in the dead weight tester is
Medium weight oil
Hydraulic comparators, which are used for testing gauges, rely on the accuracy of the
Master gauge
On a multiple steam heating system, a stop valve must be placed attach boiler outlet to
Allow boiler isolation from the system
On low pressure steam boilers, the boiler outlet valves are ussually
Gate valves because of there low resistance to flow