Chapter 8 Communications Systems Flashcards

1
Q

A circuit that extends voice, data, interactive services, telegraph, outside wiring for fire/burglar alarm and telephone/fax/answering machine from communication utility’s.

A

Communications circuit

Article 800.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

True or False
The relative location of outside overhead communications wire on the same pole as power is; below the power conductors on a separate cross-arm

A

True

Article 800.44(A)(1) and (2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

A supply service drop of 750V and below shall have a minimum separation of ____ from communications service drops at any point along the span of the drop including at their attachment to the building provided the power service is insulated and has a 40” clearance at the pole.

A

12”

Article 800.44(A)(4)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Communications cables shall have a a vertical clearance of ____ from all points of roofs above which they pass.

A

8 feet

Article 800.44(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

True or False

Underground communications cables can share a handhold or manhole enclosure without any separating barriers.

A

False

Article 800.47(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

A separation of ____ shall be maintained between communications wires on buildings and lightning conductors.

A

6 feet

Article 800.53

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

True or False
Metal raceways or conduits that allow communications cables to enter a building before the primary protector shall be grounded

A

True

Article 800.50(C)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

True or False

Raceway fill requirements of Chapter 3 and 9 apply to communications cable.

A

False

Article 800.110(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Horizontal cable routing assemblies shall be supported at intervals not to exceed ____, and at each joint,unless listed for other intervals. In no case shall the distance exceed ____.

A

3 feet. 10 feet

Article 800.110(C)(1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Vertical runs of cable routing assemblies shall be supported at intervals not exceeding ____ unless listed otherwise, and have no more than 1 joint between.

A

4 feet

Article 800.110(C)(2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly