Chapter 8 Communications Systems Flashcards
A circuit that extends voice, data, interactive services, telegraph, outside wiring for fire/burglar alarm and telephone/fax/answering machine from communication utility’s.
Communications circuit
Article 800.2
True or False
The relative location of outside overhead communications wire on the same pole as power is; below the power conductors on a separate cross-arm
True
Article 800.44(A)(1) and (2)
A supply service drop of 750V and below shall have a minimum separation of ____ from communications service drops at any point along the span of the drop including at their attachment to the building provided the power service is insulated and has a 40” clearance at the pole.
12”
Article 800.44(A)(4)
Communications cables shall have a a vertical clearance of ____ from all points of roofs above which they pass.
8 feet
Article 800.44(B)
True or False
Underground communications cables can share a handhold or manhole enclosure without any separating barriers.
False
Article 800.47(A)
A separation of ____ shall be maintained between communications wires on buildings and lightning conductors.
6 feet
Article 800.53
True or False
Metal raceways or conduits that allow communications cables to enter a building before the primary protector shall be grounded
True
Article 800.50(C)
True or False
Raceway fill requirements of Chapter 3 and 9 apply to communications cable.
False
Article 800.110(B)
Horizontal cable routing assemblies shall be supported at intervals not to exceed ____, and at each joint,unless listed for other intervals. In no case shall the distance exceed ____.
3 feet. 10 feet
Article 800.110(C)(1)
Vertical runs of cable routing assemblies shall be supported at intervals not exceeding ____ unless listed otherwise, and have no more than 1 joint between.
4 feet
Article 800.110(C)(2)