Article 250 Grounding And Bonding Flashcards
Electrical systems that are grounded will limit ____ imposed by lightning, line surges, or unintentional contact with higher-voltage lines and that will ____ to earth during normal operation.
voltage stabilize voltage
Article 250.4 (A) (1)
If the use of multiple grounding connections results in objectionable current and all requirements are met, one or more of the following alterations may be permitted;
(1) discontinue 1 or more but NOT ALL connections
(2) change locations of the connections
(3) interrupt the continuity of the conductive path
Article 250.6 (B)
Machine screw-type fasteners and thread-forming machine screws must engage no less then ____ to properly bond a connection.
Two threads
Article 250.8 (A)
The following ac systems of 50v to 1000v shall be permitted, but not required to be grounded.
(1) Electrical systems used exclusively to supply industrial electric furnaces for melting, refining, tempering and the like.
(2) separately derived systems used exclusively for rectifiers that supple only adjustable-speed industrial drivers.
Article 250.21 (A)
The following circuits shall not be grounded.
(1) circuits for electric cranes operating over combustible fibers in Class III locations.
(2) circuits in health care facilities as provided in 517.61 and 517.60
(3) circuits for equipment within electrolytic cell line working zones as provided in 668
(4) secondary circuits of lighting systems as provided in 411.6(A) and 680.23(A) (2)
(5) Class II load side circuits for suspended ceiling low-voltage power grid distribution systems as provided in 393.60(B)
Article 250.22
The grounding electrode conductor connection meant for grounding service-supplied AC systems can be made at any accessible point between ____.
the load end of the service lateral and the service disconnecting means. This includes the bussing that the grounded service conductor is connected to.
Article 250.24 (A) (1)
True or False
A dual-fed service may utilize a single grounding electrode conductor connection to the tie point of the grounded service conductors from each power source.
True
Article 250.24 (A) (3)
True or False
The main bonding jumper may have multiple splice points between the bonded conductor and the equipment grounding conductor.
False
Article 250.24 (B)
If the ungrounded service entrance conductors are installed in ____the grounded conductor shall also be installed in ____. The size of the grounded conductor in each raceway shall be based on the total circular mil area of the ungrounded conductors in the raceway, but no smaller than ____.
Parallel Parallel 1/O AWG
Article 250.24 (C) (2)
A common grounding electrode conductor taped to multiple separately derived systems shall be permitted to be one of the following ____.
(1) not smaller than 3/O AWG
(2) a metal water pipe
(3) the metal structural frame of the building
Article 250.30 (A) (6)
Tap connections to a common grounding electrode conductor shall be made by one of the following methods.
(1) connector listed as grounding and bonding equipment
(2) listed connections to busbar not smaller than 1/4” thick x 2” wide
(3) exothermic welding
Article 250.30 (A) (6)
A metal underground water pipe must be in direct contact with the earth for ____ or more to be a permitted grounding electrode.
10’
Article 250.52 (A) (1)
A metal in-ground support structure must be in direct contact with the earth vertically for ____ or more to be a permitted grounding electrode.
10’
Article 250.52 (A) (2)
A concrete encased electrode shall consist of at least 20’ of either;
(1) one or more bare or zinc galvanized coated steel reinforcing bars or rods of not less than 1/2” diameter, installed in a continuous length or connected by steel tie wires.
(2) bare copper conductor not smaller than 4 AWG
Article 250.52 (A) (3)
A ground ring encircling the building or structure, in direct contact with the earth, must consist of at least ___ of bare copper conductor not smaller than ____.
20’ 2 AWG
Article 250.52 (A) (4)
Rod and pipe electrodes shall not be less than ____ in length and consist of either; conduit no less than ____ and have the outer surface metal coated for corrosion protection, or a rod-type electrode that is stainless steel and copper or zinc coated steel no less than ____ in diameter.
8’ trade size 3/4” 5/8”
Article 250.52 (A) (5)
Plate electrodes shall expose no less than ____ of surface to the exterior soil. Bare or electrically conductive coated iron/steel plates shall be at least ____ in thickness
2’ 1/4”
Article 250.52 (A) (7)
The following materials shall not be used as grounding electrodes.
(1) metal underground gas piping systems
(2) aluminum
Article 250.52 (B)
If practicable, rod, pipe, and plate electrodes shall be embedded below ____.
permanent moisture level
Article 250.53 (A) (1)
If a single rod, pipe, or plate electrode has a resistance to earth of ____ or less, a supplemental electrode shall not be required.
25 ohms
Article 250.53 (A) (2)
If multiple supplemental electrodes are installed to meet requirements, they shall not be less than ____ apart.
6’
Article 250.53 (A) (3)
The bonding jumper that is the sole connection to the supplemental rod, pipe, or plate electrode shall not be required to be larger than ____.
6 AWG
Article 250.53 (E)
The ground ring shall be installed not less than ____ below the surface of the earth.
30”
Article 250.53 (F)
Plate electrodes shall be installed not less than ____ below the surface of the earth.
30”
Article 250.53 (H)