Chapter 7: Sanitary Drainage Flashcards
The maximum fixture unit loading allowed on a 2-inch waste stack is ________.
Sixteen fixture units
Three-inch horizontal drainage piping shall have a grade or slope of not less than ________.
1/4 inch per foot
The maximum trap loading for a 3-inch trap is ___________.
Six units
The minimum sizes of verticalk and horizontal drainage shall be determined from the __________.
Total fixture units
The minimum size trap and trap arm for a bathtub is ___________.
1-1/2 inches
The maximum discharge capacity (for intermittent flow only), in gallons per minute, for one fixture unit is equal to ______.
7-1/2 gallons per minute
The minimum size drain line for a wall-hung urinal is _______ inches.
2 inches
The acceptable fitting for connecting a horizontal drain line with another horizontal drain line is a ___________.
Combination wye and 1/8 bend
The clearance required in front of a 2-inch clean out shall not be less than_________.
12 inches
The discharge line from an ejector shall be provided with a _____________.
Backwater or swing check valve, and gate valve
The minimum size discharge pipe from an ejector of pump in a single dwelling unit having a water closet connected thereto is ___________________.
2 inches
A horizontal drain pipe has an existing load of 30 fixture units, after connecting the discharge pipe from an ejector rated at 60 gallons per minute, the total load on the horizontal drain pipe will be ___________.
150 fixture units
Because of structural conditions, a 4-inch building drain is installed with a slope of 1/8 inch per foot. The installation will result in ______________.
A reduction in fixture unit load allowance
_______________ are considered suds-producing fixtures.
Kitchen sinks, bathtubs, and washing machine standpipes
Drainage connections shall not be made into a drainage piping system within __________ of any vertical to horizontal change of direction of a stack containing suds-producing fixtures.
8 feet