Chapter 6 - Tightness Testing & Purging Flashcards

1
Q

Tightness Testing & Purging document and current Edition?

A

IGEM/UP/1B

Edition 3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Total installation volume (IV) of any meters, pipework and fittings supplying any individual dwelling must not exceed?

A

Max IV - 0.035 m³

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What 4 things for permissible drop

Permissible drop is drop in pressure a small gas escape.

A

• Size of the meter/type
• Diameter of the Pipework
• Existing appliance or appliances
• No smell of gas

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Purge Procedure

Less than 0.02 m³ ?
More than 0.02 m³ ?

A

Less than; The gas may be purge either through an open burner or loosened fitting (crack a union) on the gas installation

Greater than; The gas shall be purged through an open burner with a constant source of ignition.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When purging which appliance should be used?

A

The furthest appliance away from the meter.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When testing the working pressure which appliance should be used?

A

The biggest KW appliance.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly