Chapter 6 - Tightness Testing & Purging Flashcards
Tightness Testing & Purging document and current Edition?
IGEM/UP/1B
Edition 3
Total installation volume (IV) of any meters, pipework and fittings supplying any individual dwelling must not exceed?
Max IV - 0.035 m³
What 4 things for permissible drop
Permissible drop is drop in pressure a small gas escape.
• Size of the meter/type
• Diameter of the Pipework
• Existing appliance or appliances
• No smell of gas
Purge Procedure
Less than 0.02 m³ ?
More than 0.02 m³ ?
Less than; The gas may be purge either through an open burner or loosened fitting (crack a union) on the gas installation
Greater than; The gas shall be purged through an open burner with a constant source of ignition.
When purging which appliance should be used?
The furthest appliance away from the meter.
When testing the working pressure which appliance should be used?
The biggest KW appliance.