Chapter 11 Flue/Chimney systems Flashcards
A circular flue for a new gas fire requires a minimum cross-sectional area of what?
12,000 mm² this is the same as 5 inches or 125 mm
What is meant by natural draught appliance?
No fan to get products of combustion out or air in.
ACS exam question
If an appliance has a dodgy flue and products of combustion continue to enter the room is the draught diverter working?
Yes, but the flue isn’t.
Name the four points on an open flue appliance.
- Primary flue this will be covered.
- Draught diverter (Looks like a skirt).
- Secondary flue.
- Terminal.
What is the minimum length of a flue for a gas fire?
3 m straight pipe
Bends shall not exceed?
How much does a bend or a terminal reduce the height of a flue by?
There must be a minimum of how many millimetres vertical rise before the first bend?
45°
0.5 m each
600 mm
Flue twin walled will appear a dull grey colour what is between the first and second wall gap?
Air gap.
Factory insulated flue will appear very shiny or black what length can this be?
28 meters
Any opened flu appliance greater than 7 kW net will require ventilation how many cm² for every net kW above 7 kW?
5 cm²
The formula to work this out is:
Net kW -7×5 =
The appliance must incorporate a control to automatically shut down the burner if it detects no air for more than how many seconds?
Six seconds
If a chimney is 4 m high and has two 45° bends under terminal what would the height be?
2.5 m
The formula for this:
4 m - 1.5 m = 2.5 m
The bends and the terminal each equal 0.5 m .
How many metres can a single wall pipe be outside or in the loft?
0 m single wall pipe cannot be outside.
Sockets must be facing uppermost on what type of flue?
Cement based single wall flue.
Where temperatures are expected to exceed 85°? The flue pipe shall be a minimum of how many millimetres from any combustible material?
25 mm
A non-combustible sleeve may be used to provide 25 mm air gap.
BS EN 13501 - 1 : 2007 + A1:2009
Approved document B states what materials must be used in construction on external walls
Class A1