Chapter 6 (Installation of Portable Fire Extinguishers) Flashcards
Can a fire extinguisher be installed where a visual obstruction blocks its view?
Yes but only where the visual obstruction cannot be avoided and you must have signs or other means to indicate the extinguisher’s location.
what are the four acceptable means of installing a fire extinguisher other than a wheeled fire extinguisher?
(1) securely on a hanger intended for the extinguisher
(2) in a bracket incorporating releasing straps or bands supplied by the extinguisher manufacturer.
(3) in a listed bracket incorporating releasing straps or bands approved for such purpose.
(4) in approved cabinets or wall recesses
Are you allowed to fabricate hangers or brackets in the field?
No Hangers and brackets shall not be fabricated in the field.
Fire extinguishers installed in vehicles or under other conditions where they are subject to dislodgement shall____
Be installed in approved strap-type brackets specifically designed for this application.
Fire extinguishers having a gross weight NOT exceeding 40 LB shall be installed so that the top of the fire extinguisher is not more than?
5 FT above the floor
Fire extinguishers have a gross weight GREATER than 40 LB shall be installed so that the top of the fire extinguisher is not more than?
3 1/2 FT above the floor
In no case shall the clearance between the bottom of the hand portable fire extinguisher and the floor be less than?
4 in.
Fire extinguishers shall be installed so that the fire extinguisher’s Operating instructions____
Face outward
Hazardous materials identification systems (HMIS) labels, 6-year maintenance labels, hydrostatic test labels or other labels shall_______
Not be located or placed on the front of the extinguisher
Cabinets housing fire extinguishers shall not be locked, except?
Where fire extinguishers are subject to malicious use and cabinets include a means of emergency access
where fire extinguishers are installed in closed cabinets that are exposed to elevated temperatures, the cabinets shall ____
Be provided with screened openings and drains
Do the mounting height standards still apply to extinguishers stored in cabinets and wall recesses?
Yes, Extinguishers 40 lbs or less shall not be installed 5 FT above the floor from the top of the extinguisher, extinguishers greater than 40 lbs shall not be installed 3 1/2 FT above the floor from the top of the extinguisher, and in no case shall the clearance between the bottom of the extinguisher and the floor be less than 4 in.
For fire-resistance-rated walls, only _____may be installed.
surface mounted cabinets or listed fire-rated cabinets shall be installed.
Fire extinguishers containing only plain water shall be protected to temperatures as low as ______ by addition of an _____
(1) -40 degrees Fahrenheit
(2) antifreeze that is stipulated on the fire extinguisher name plate
_____ solutions shall not be used in stainless steel fire extinguishers.
calcium chloride
How do you determine the minimum number of Class A fire extinguishers needed for each floor of a building?
you divide the total floor area by the maximum area to be protected per extinguisher.