Chapter 4 (general requirements) Flashcards
what are the four things that a fire extinguisher shall be marked with?
(1) Identification of the listing and labeling organization
(2) product category indicating the type of extinguisher
(3) extinguisher classification
(4) performance and fire test standards that the extinguisher meets or exceeds
Fire extinguishers manufactured prior to __________ shall not be required to comply with 4.1.2 and 4.1.3
January 1, 1986
An organization listing fire extinguishers used to comply with the requirements of this standard shall utilize a __________for portable fire extinguishers that meets or exceeds _______.
(1) Third-party certification program
(2) UL 1803
Extinguishers listed for the class c rating shall
Not contain an agent that is a conductor of electricity
water-based agents, that are listed for the class c rating shall be tested in accordance with?
ASTM D5391
Fire extinguishers containing water based agents that have a conductivity higher than ______ at _______ shall be considered a conductor of electricity and therefore shall not be rated class c
1.00 micro Siemens per centimeter (μS/cm) at 25°C (77°F)
what six pieces of information need to be on the label, tag, or stencil attached to the fire extinguisher?
(1) contents product name
(2) listing of the hazardous material identification
(3) List of any Hazardous materials in excess of 1.0 percent of contents
(4) list of any chemical in excess of 5.0 percent of contents
(5) Information about what is hazardous about the agent
(6) Manufacturer’s or service agency’s name, mailing address, and phone number
The ________shall be provided with a fire extinguisher manual that details condensed instructions and cautions necessary to the ________
(1) owner or owner’s agent
2) installation, operation, inspection, and maintenance of the fire extinguisher(s
what are the 13 types of obsolete fire extinguishers?
(1) Soda acid
(2) Chemical Foam
(3) Carbon Tetrachloride, methyl bromide, and Chlorobromomethane (CBM)
(4) cartridge-operated water
(5) cartridge-operated Loaded stream
(6) copper or brass shall joined by soft solder or rivets
(7) carbon dioxide extinguishers with metal horns
(8) solid charge-type AFFF extinguishers
(9) pressurized water fire extinguishers manufactured prior to 1971
(10) any extinguisher that needs to be inverted to operate
(11) any extinguisher manufactured prior to 1955
(12) any extinguisher with 4b,6b,8b,12b, and 16b fire ratings
(13) store-pressure water extinguishers with fiberglass shells (pre-1976)
Dry chemical store-pressure extinguishers manufactured in 1984 or prior shall be _____ unless____
removed from service
they are the wheeled type
Any fire extinguisher that can no longer be serviced in accordance with the _______ is considered ________
Manufacturer’s maintenance manual
Obsolete and shall be removed from service