Chapter 17 - ESS Flashcards
To ensure general audibility, in the United States, NFPA 72 require that public mode fire alarm signaling achieves output levels of ___ over average ambient sound (dBA) levels.
a. 20 dB
b. 15 dB
c. 10 dB
d. 5 db
b. 15 dB
p 17-27
Codes and standards contain extensive rules and guidelines to address these issues. To ensure general audibility in the United States, NFPA 72® requires that public mode signaling achieves output levels of 15 dB over average ambient sound (dBA) levels, or 5 dB over the maximum dBA level having duration of at least 60 seconds in all areas of protected premises.
A typical electronic access control (EAC) cable consists of four ___ that are used for the door strike, card reader, door contact, and request for exit.
a. Twisted pairs surrounded by an overall shield
b. Strands of multimode optical fiber
c. Unshielded twisted pairs
d. Individually shielded pairs
d. Individually shielded pairs
p 17-10
EAC systems may be part of a converged network and utilize the structured cabling system for connectivity and power. An analog-type EAC cable consists of four individually shielded pairs.
The four individual wire pairs may be supplied individually or in a group. Colored foil shields or jacket colors may be used to designate the intended purpose of each of the wire pairs within the cables.
At a minimum, both transmission channels for a digital alarm communicator transmitter (DACT) must be tested at regular intervals not exceeding one week.
a. True
b. False
b. False
p 17-50
Both transmission channels are tested at regular intervals not exceeding 24 hours. If two telephone lines are used, it is permitted to test each telephone line at alternating 24-hour intervals.
For public cellular telephone service, transmit a test signal at least monthly.
In terms of lock types, A grade ___ lock has been tested to be more durable than a grade ___.
a. 1, 2
b, 2, 1
a. 1, 2
p 17-13
The term grade is often used to classify hardware by durability. A grade 1 lock has been tested to be more durable than a grade 2. A grade 2 has been tested to be more durable than a grade 3.
Electric strike’s unlock time, ___ to ___ seconds, is normally set by the EAC system headend .
a. 2, 6
b. 4, 10
c. 8, 11
d. 10, 14
c. 8, 11
p 17-14
- Electric strike’s unlock time, 8 to 11 seconds, is normally set by the EAC system headend.
- Electric strikes are matched and shall be compatible to the type of locking hardware employed (see Figure 17.5). This may simply be the function of selecting the appropriate faceplate.
Magnetic lock door release devices are required the means of release be mounted within approximately ___ ft of the door at a height between approximately ≈1016 mm (40 in) and ≈1220 mm (48 in) AFF, respectively.
a. 3
b. 4
c. 5
d. 6
c. 5
p 17-16
Codes normally require the means of release be mounted within approximately ≈1.5 m (5 ft) of the door at a height between approximately ≈1016 mm (40 in) and ≈1220 mm (48 in) AFF, respectively.
Mount interior cameras to clear ___ ft AFF while exterior cameras should maintain a minimum of ___.
a. 8, 14
b. 8, 15
c. 9, 14
d. 9, 15
b. 8, 15
p 17-23
Mount interior cameras to clear ≈2.4 m (8 ft) AFF while exterior cameras should maintain a minimum of ≈4.6 m (15 ft). These heights are recommended to prevent intentional and accidental tampering with the camera
Video surveillance matrix switches traditionally are available in multiples of 16 or 32 inputs and outputs.
a. True
b. False
b. False
p 17-24
The traditional product is available in multiples of 8 or 16 inputs and outputs
Within a recording server, the frame rate for any given application is custom to each situation, but a general rule is never to accept less than ___ fps.
a. 3.75
b. 5
c. 7.5
d. 10
a. 3.75
p 17-26
The normal frame rates used are 1 fps, 3.75 fps, 7.5 fps, 15 fps, and 30 fps. The frame rate for any given application is custom to each situation, but a general rule is never to accept less than 3.75 fps.
The traditional video surveillance camera outputs up to 470 lines of resolution; therefore, the ___ CIF is close to the native camera resolution.
a. 2
b. 4
b. 4
p 17-26
The traditional video surveillance camera outputs up to 470 lines of resolution; therefore, the 4CIF is close to the native camera resolution.
The current standard resolutions for National Television System Committee are:
• Common intermediate format (CIF [320 × 240]).
• 2CIF (320 × 480).
• 4CIF (640 × 480).
The number of incoming telephone lines to a digital alarm communicator receiver (DACR) is limited to ___ lines.
a. 20
b. 12
c. 8
d. 5
c. 8
p 17-52
The number of incoming telephone lines to a DACR is limited to eight lines.
If any digital alarm communicator transmitter (DACT) signal transmission is unsuccessful, the information is transmitted by used of the digital alarm radio transmitter (DART). The DART must be capable of demonstrating a minimum _____ percent probability of successfully completing each transmission sequence.
a. 90
b. 85
c. 95
d. 99
a. 90
p 17-51
The DART is capable of demonstrating a minimum 90-percent probability of successfully completing each transmission sequence. Transmission sequences are repeated a minimum of five times.
___ detectors sense visible or invisible particles of combustion generated by burning, smoldering, or the incipient stage of combustion. These devices fall into two categories—photoelectric and ionization.
a. Smoke
b. Flame
c. Heat
a. Smoke
p 17-33
___ detectors sense the radiation produced by fire (e.g., visible light or invisible radiation, IR, ultraviolet radiation).
a. Smoke
b. Flame
c. Heat
b. Flame
p 17-33
AHJs typically will require pull stations that are located within ___ ft of each door that is a point of egress.
a. 2
b. 3
c. 4
d. 5
d. 5
p 17-34
AHJs typically will require pull stations that are located within ≈1.5 m (5 ft) of each door that is a point of egress and are strategically placed so that the linear travel distance between pull stations does not exceed ≈61 m (200 ft).
Pull stations typical mounting heights of pull stations should be ___ in to ___ in above the floor.
a. 36, 42
b. 40, 50
c. 42, 52
d. 48, 54
d. 48, 54
p 17-34
Notification appliances used for FA signaling are almost exclusively designed to operate on ___ V dc power.
a. 12
b. 24
c. 48
b. 24
p 17-36
Notification appliances used for FA signaling are almost exclusively designed to operate on 24 V dc power so that they will continue to function normally on battery backup power in the event of a loss of primary power from the FA system.
To ensure general audibility, in the United States, NFPA 72 require that public mode fire alarm signaling achieves levels 5 dB over the maximum dBA level having a duration of at least ___ seconds in all areas of protected premises.
a. 15
b. 30
c. 60
d. 90
c. 60
p 17-37
ensure general audibility in the United States, NFPA 72® requires that public mode signaling achieves output levels of 15 dB over average ambient sound (dBA) levels, or 5 dB over the maximum dBA level having duration of at least 60 seconds in all areas of protected premises.
According to the FA intelligibility standard, effective systems should exceed the equivalent of a CIS score of ___.
a. 0.50
b. 0.60
c. 0.70
d. 0.80
e. 0.90
c. 0.70
p 17-38
According to the standard, effective systems should exceed the equivalent of a CIS score of 0.70. As the popularity of voice evacuation systems increases, the standard for intelligibility will become more widely understood and tested.
Depending on the required functions and considerations, the control units are usually ___-based and require software to process data and make decisions.
a. Field level
b. System level
c. Headend
d. Microprocessor
d. Microprocessor
p 17-39
Depending on the required functions and considerations, the control units are usually microprocessor-based and require software to process data and make decisions.
Control units are capable of two-way communications. The units receive, process, and make detection decisions based on processed data to transmit commands to alarm and control devices.
For circuit and pathway designations, Class ___ circuits have fail-safe operation, where no fault is annunciated, but the intended operation is performed in the event of a circuit failure.
a. A
b. B
c. C
d. D
e. E
f. X
g. N
d. D
p 17-41
These circuits typically include the wiring that provides power to magnetic door holders (e.g., interruption of the power results in the door closing).
For circuit and pathway designations, Class ___ does not include a redundant signal pathway and operational capability stops at a single open in the circuit.
a. A
b. B
c. C
d. D
e. E
f. X
g. N
b. B
p 17-41
Conditions that affect the intended operation shall result in an annunciation of a trouble signal. A single ground fault does not affect operational capability but shall also be annunciated as a trouble signal.