Chapter 15 Flashcards
The road test must be conducted at what weight?
Conducted with the vehicle loaded to the same weight as it will be when placed in service.
For the road test the vehicle must be able to achieve at least a top speed of?
50 mph
Apparatus must accelerate to 35 mph from a standing start within how many seconds?
25 seconds
Apparatus must come to a full stop from 20 mph within how many feet?
35 ft
The pump body as well as the entire intake and discharge piping system, with the exception of the tank fill and tank-to-pump lines on the tank side of the valves, are subjected to a minimum hydrostatic test pressure of_ for a minimum of _?
Minimum hydrostatic pressure of 500 psi, for a minimum of 10 mins
Apparatus testing is?
Preserve test on fire apparatus or equipment performed at the factory or after delivery to assure the purchaser that the apparatus meets bid specifications
Performance testing should be done how often?
At least once each year, or whenever it has undergone major pump or powertrain repair
Per NFPA 1911 specifies that all gauges used for service testing must be calibrated within how many days of testing?
Within 60 days
For the vacuum test, is the pump fails to reach how many inches of mercury, the apparatus should be removed from service until repairs can be made?
If the apparatus fails to reach 22 inches of mercury
Per NFPA 1911 fire pumps of 1250 gpm capacity must achieve prime in how many seconds or less? Those rated 1500 gpm must be primed within how many?
1250 - 30 seconds or less
1500 - 45 seconds or less
With the tank to pump flow test, pumpers with an onboard tank capacity of 500 gallons or less must be capable of flowing how many GPMs from their onboard tank?
250gpm
With the tank to pump flow test, pumpers with a capacity greater than 500 gallons must be capable of flowing how many GPMs?
At least 500 gpm
Any apparatus that achieves less than 90 percent of its original rated capabilities has two options for continued use which are?
Placed out of service and restored to its original capabilities and tested again. Or the apparatus may be given a lower rating based on the results of the most recent testing.
The methods for testing a foam proportioning system for calibration accuracy are?
Foam concentrate displacement method, foam concentrate pump discharge volume method, foam solution reactivity testing, and foam solution conductivity testing
The formula for percent of concentrate in solution is
Percent of concentrate in solution= (conductivity of solution)-(conductivity of water)/ 500