Chapter 11 Flashcards

1
Q

A(n) ___ is the operation of equipment in excess of normal, full-load current rating, or a conductor subject to a current in excess of the rated ampacity.

A

Overload

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The branch-circuit conductors on the line side of the controller for a multispeed motor shall be sized at ___% of the highest of the FLC ratings shown on the motor nameplate.

A

125

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

A/C units that operate at ___ or less may be cord-and-plug-connected.

A

250 V, 1Ö

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

If the service factor and temperature rise are not marked on the nameplate, the nameplate current should be multiplied by ___%.

A

115

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The winding type shall be given on the nameplate of a DC motor.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The overcurrent protection for an MCC may be located ahead or within the MCC.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Table ___ is used to determine the current ratings of 3Ö AC motors.

A

430.250

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The ___ branch circuit is the point from the last fuse or circuit breaker protecting the motor circuit out to the motor.

A

Motor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The code letter or locked-rotor amps shall be listed on the nameplates of motors rated ___ HP or more.

A

.5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

The rated frequency shall be given on the nameplate of a motor controller.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Small motors rated 150 W or less shall be marked “Impedance Protected.”

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Equipment shall be located within ___’ and be visible to be considered within sight.

A

50

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Cord-and-plug-connected compressors and equipment shall be rated no greater than ___ A on 120 V circuits.

A

20

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The larger a motor’s full-load table current, the less the percentage of the increase in sizing the thermal protector that is an integral part of the motor.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Branch-circuit conductors supplying a single motor shall have an ampacity of ___% of the FLC rating as indicated on the appropriate FLC table.

A

125

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

The ampere rating of a fusible disconnect is determined by the size of fuse being used in the motor branch circuit.

A

True

17
Q

Motor nameplates shall include the rated horsepower if ___ HP or more.

A

1-8

18
Q

The disconnecting means for motor circuits are required to have an ampere rating of at least ___% of the FLC rating of the motor for circuits rated 1000 V or less.

A

115

19
Q

A(n) ___ device is a pilot light, buzzer, horn, or other type of alarm.

A

Indicating

20
Q

A(n) ___ refrigerant motor-compressor is a combination compressor and motor enclosed in the same housing, having no external shaft or shaft seals, with the motor operating in the refrigerant.

A

Hermetic

21
Q

A ___ is an assembly of one or more enclosed sections with a common power bus and primarily containing motor control units.

A

Motor control center

22
Q

The ___ is the device in a motor circuit which turns the motor ON or OFF.

A

Controller

23
Q

A plug and receptacle may serve as a controller for stationary motors up to 2 HP.

A

False

24
Q

A/C and refrigeration equipment with several motors can be considered as a single machine.

A

True

25
Q

The length of flexible cords used to supply A/C units shall not exceed ___’ for 120 V units.

A

10