Ch.3-1-A
TE (telecommunication enclosure)
A CASE
CH.3-1.B
QUESTION:
A case serves what size area?
3600 SQFT OR 36 work Areas
CH.3-1.D
QUESTION
A TE supports ?
36 work areas
CH.3-1.F
QUESTION : A work area for EVERY?
100 SQFT
CH.3-1.G
QUESTION:
A TR ( TELECOMMUNICATIONS ROOM ) =
ARCHITECTURAL SPACE (PASSIVE SPACE)
CH.3-1.H
Question:
An “ER” is an Equipment room=
Environmentally Controlled
CH.3-1.I
Question:
An “EF “ is a ENTRANCE FACILITY =
OSP
CH.3-3.A
Question:
What is the minimum ceiling height for a telecommunication space?
8 Feet
CH.3-3.B
Question:
If available, what is the considered height for a telecommunication space?
10 feet
(52) CH.3-3.A
Question:
All Clearances =
3.28 ft
(52) CH.3-3.C
Question:
What’s the minimum depth from the wall to the wall mounted equipment?
6 inches
(52) CH.3-3.E
Question:
What is the amount of cycle is required from the equipment to the corners?
12 inches
(53) CH.3-4.B
Question:
What is the minimum size in quantity of conduits and sleeves used for backbones pathways for TR,ER and EF’s
A minimum (4) 4” CONDUITS
(53)CH.3-4.D
Question:
How many conduit are required to connect to telecom rooms on the same floor?
(2) 4” CONDUITS
(54) CH.3-5.B
Question:
What is the size of the door for a telecommunication room?
3 feet
(54) CH.3-5. BB
Question:
What is the size of the door for a HEAVY EQUIPPED telecommunication room?
Must be 6 feet wide
(55) CH.3-6.A
Question:
TR EQUIPMENT POWER=
2 DEDICATED POWER OUTLETS ABOVE EACH EACK
(55) CH.3-6.B
Question:
TR CONVENIENCE OUTLETS=
6” AFF OUTLETS EVERY 6’ AROUND PERIMETER OF THE ROOM
(55) CH.3-6.B.1
Question:
How many air changes are in a tunnel?
Three air changes per hour
(55) CH.3-6.B.2
Question:
How many air changes in a room?
One air change per hour