Ch 9 Add 1 HIGH-PRESSURE PUMPING OPERATIONS Flashcards

1
Q

 High-Pressure Engines: Two-stage 1000 gpm or 2000 gpm engines retro-fitted with
a ____________ and have been issued specialized highpressure
equipment to pump at discharge pressures over ____ psi and up to ____ psi.

A

a special high-pressure discharge elbow,
250psi , 600psi
Sec 1.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

3rd Stage Engines: An engine with a 3rd Stage. This 3rd Stage can supply a maximum
of ____ gpm up to ____ psi.

A

500 , 700
Sec 1.1

357

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

High-pressure and 3rd-stage engines have the following specialized equipment ?

A

 3” high-pressure supply hose, 50’ per length.
 High-pressure fittings. (painted white, heavier)
 High-pressure outlets.
o One HP outlet on HP Engines.
o Two HP outlets on 3rd Stage Engines.
 Tether straps with gated hooks.
Sec 1.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Can conventional engines operate in excess of 250 psi ?

A

YES!
Unless emergency conditions exist AND they are ordered to do so by the IC,
conventional engines should not operate in pressures exceeding 250 psi
Sec 1.4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fire on the 75th floor , what is the operating pressure needed ?

A

500psi doofus

Check Table 2 in Sec 2.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

At what pressure is to be considered High Pressure Operations ?

A

Excess of 250 psi!

Sec 2.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Prior to starting high-pressure pumping what must first be established ?

A

A safety zone must be established on each side
of the engine and high-pressure supply hose. Warning tape, rope or stanchions are to be
used to designate this zone
Sec 3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Maintain safety zones of at least _____ around a working engine in all directions
including the high-pressure supply hose.

A

50 feet

Sec 3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When using high pressure hose for high pressure pumping no more than 3 lengths shall be stretched from pumper to siamese. Agree or Disagree

A

Disagree fool!!
Whenever possible, an engine supplying high-pressure should be positioned within 1 hose
length of the fire department connection being supplied.
No more than 2 connected lengths
of high-pressure supply hose should be stretched to the fire department connection
Sec 3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

In an extreme emergency High pressure or 3rd stage pumpers can use standard 3 1/2” as a supply line. True or False

A

FALSE!! MUST USE
Specially trained and equipped ‘High-Pressure’ or ‘3rd Stage’ engines MUST use their
high-pressure supply hose, fittings (painted white and noticeably heavier than
conventional fittings) and tether strap
Sec 3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When operating in high pressure should the gates and outlets be closed ?

A

YES!!
All unused gates and outlets on the apparatus MUST be closed and capped. All caps must
be secured tightly.
Sec 3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Each engine operating at high-pressure must be controlled by the ECC and assisted by Who ? And shall do what ?

A

ECC from a non-pumping engine. One ECC shall operate the pump and one ECC shall
monitor radio communications. Other ECCs of non-pumping engines shall assist in
keeping persons out of the safety zone.
Sec 3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

High pressure hose MUST be secured using the tether straps . At what points are the secured ? 1-3 What if tether straps unavailable ?

A

The tether strap shall be secured to
both the engine and the building fire department connection.
When more than one length of hose is required, each length must be tethered and secured
to each other by the tether gated hook
No Tether use utility rope! secure apparatus and siamese
Sec 3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

During high pressure ops. stairwells served by standpipes are a good place to use as a rest area so as members can monitor system ?

A

NO!!
Stairwells served by standpipes must not be used as staging or rest areas during high
pressure pumping operations. Use a minimum amount of operating personnel in these
stairways.
Sec 3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Preset pressures on apparatus equipped with pressure governors, should be used when
charging a standpipe system. Agree or Disagree

A

Disagree!!
Preset pressures on apparatus equipped with pressure governors, should not be used when
charging a standpipe system. Once the supply line is charged, pressures are to be
increased slowly to avoid damage to the building piping.
Sec 3.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When more than one eng supplies a standpipe it is good practice for one engine to supply at a pressure 20 psi lower than the other ?

A

No!!
When more than one engine supplies the standpipe system, ECCs shall communicate and
coordinate to ensure that they operate at the same discharge pressure.
Sec 3.1

17
Q

Officers must be aware of the potential need for high-pressure pumping operations and
the pumping capabilities of responding engines. When other than 1st due where shall officers direct ECC’s to position rigs?

A

When other than first due to a fire in a
high-rise building, officers of high pressure Engines and 3rd Stage Engines shall direct
their ECCs to position the apparatus at a hydrant in proximity to the standpipe siamese
Sec 3.1

18
Q

The standpipe system should be supplied by two engines. This will require more than
one high-pressure or 3rd Stage Engine to be assigned or special called to the incident if
pressures higher than 250 psi are required. Where shall the 2nd supply line go ?

A

When only one building siamese connection
is available, stretch the second supply line to the first floor outlet.
DO NOT connect TWO
high-pressure supply lines to a single building siamese connection.
Sec 3.1

19
Q

Pressures exceeding ____ psi will REQUIRE a 3rd stage engine. When 3rd stage pumping is
implemented, the IC shall ensure an additional 3rd Stage Engine is assigned to the incident.
As a heads up LT and the IC at the fire You order your ECC to engage the 3rd stage for pumping. Correct ?

A

600psi
NOO!!
ECCs intending to pump using the 3rd stage must notify and get approval from the IC. Only
an IC at the rank of Battalion Chief or higher may order the use of the 3rd stage.
Sec 4.1Over 600 psi 3rd stage REQUIRED
Over 500 psi 3rd stage is PREFERRED

20
Q

For pumping in excess of 500 psi . What pumper is preferred ?

A

As compared to two-stage engines, three-stage engines (with the third stage engaged) can
pump higher volumes at pressures over 500 psi and will do so at lower pump rpm’s.
This increased efficiency makes the 3rd Stage Engines the PREFERRED choice for pumping
operations requiring discharge pressures over 500 psi
Sec 4.2
Over 600 psi 3rd stage REQUIRED
Over 500 psi 3rd stage is PREFERRED