Ch. 6: Installation of Fire Extinguishers Flashcards
In what ways can a fire extinguisher be installed?
(1) On a hanger intended for the extinguisher
(2) In a bracket having straps or bands supplied by the extinguisher manufacturer
(3) In a listed bracket having approved straps or bands
(4) In approved cabinets or wall recesses
For fire extinguishers weighing less than 40 pounds what shall be the max installed height of the top of the extinguisher?
5 feet
For fire extinguishers weighing more than 40 pounds what shall be the max installed height of the top of the extinguisher?
3.5 feet
What is the minimum clearance required from the base of the extinguisher to the floor?
At least 4 inches
When installing a fire extinguisher, in what direction must the operation instructions face?
The operation instructions must face outward
Fire extinguishers containing only plain water shall be
protected to temperatures as low as _____ by the addition of an antifreeze that is stipulated on the fire extinguisher nameplate.
−40°F
Class A fire extinguishers shall be located so that the maximum travel distances shall not exceed ____.
75 feet
Up to _____ of the complement of Class A fire extinguishers shall be permitted to be replaced by
uniformly spaced 1.5 inch hose stations for use by the occupants of the building.
One half of the required Class A extinguishers can be replaced by hose stations.
True or False: For Class A hazards, two lower rated extinguishers are permitted to replace an extinguisher of a higher rating (such as two 2.5 gallon extinguishers meeting the requirements of a 4A extinguisher).
True
Class B fire extinguishers shall be located so that the maximum travel distances shall not exceed ____.
50 feet
Portable fire extinguishers shall not be installed as the
sole protection for flammable liquid hazards of appreciable depth where the surface area exceeds ____ square feet.
10 sqft (or 20 sqft when trained personnel are capable of responding immediately)
True or False: For Class B hazards, two lower rated extinguishers are permitted to replace an extinguisher of a higher rating
False
What is the max travel distance for hand portable fire extinguishers that are installed for obstacle, gravity/three-dimensional, or pressure fire hazards?
30 feet
For wheeled fire extinguishers of 125 lb agent capacity or larger that are installed for obstacle, gravity/three-dimensional, or pressure fire hazards, what is the max travel distance to the hazard?
100 feet
For Class D hazards, what is the max travel distance from the hazard to the nearest extinguisher?
75 feet