Table 220.42 demand factors for dwelling units
First 3000va at 100%
From 3001 to 120000 at 35%
Remainder over 120000 at 25%
A demand factor of ___% can be applied to appliances that are fastened in place
75
The calculated load for a dryer must be ___va or nameplate, whichever is higher
5000
Service conductors supplying a single dwelling unit may have its ampacity sized to ___% of the service overcurrent device rating
83
The neutral load for household cooking equipment is considered ___% of the calculated load
70
The demand factors for general loads for the optional method are
The first 10kVA at 100%
The remainder at 40%
When using the optional method for a dwelling unit service calculation, the only connected load not subject to the demand factors are the ___
Heat/AC loads
The smallest allowable service size for a dwelling unit
100a
An example of linear lighting load
Incandescent
Sections
Taps for Branch Ckts
Taps for feeders
- 19
240. 21
Heat/AC for optional method
A/C ___
Heat ___
3 or less heat ___
4 or more heat ___
100%
65%
65%
40%
Lighting ckt capacity equations
Noncontinuous loads
Continuous loads
OCPD x Volts = Va capacity
OCPD x Volts x 80% = Va capacity
The minimum va for a mobile home lot
16000va
Table - demand factors for mobile homes
550.31
Areas where lighting are not considered continuous
Dwelling units
Motel rooms