Calculations for Dwelling Units Flashcards

1
Q

Table 220.42 demand factors for dwelling units

A

First 3000va at 100%
From 3001 to 120000 at 35%
Remainder over 120000 at 25%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A demand factor of ___% can be applied to appliances that are fastened in place

A

75

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The calculated load for a dryer must be ___va or nameplate, whichever is higher

A

5000

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Service conductors supplying a single dwelling unit may have its ampacity sized to ___% of the service overcurrent device rating

A

83

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The neutral load for household cooking equipment is considered ___% of the calculated load

A

70

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The demand factors for general loads for the optional method are

A

The first 10kVA at 100%

The remainder at 40%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When using the optional method for a dwelling unit service calculation, the only connected load not subject to the demand factors are the ___

A

Heat/AC loads

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The smallest allowable service size for a dwelling unit

A

100a

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

An example of linear lighting load

A

Incandescent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Sections

Taps for Branch Ckts
Taps for feeders

A
  1. 19

240. 21

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Heat/AC for optional method

A/C ___
Heat ___
3 or less heat ___
4 or more heat ___

A

100%
65%
65%
40%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Lighting ckt capacity equations

Noncontinuous loads
Continuous loads

A

OCPD x Volts = Va capacity

OCPD x Volts x 80% = Va capacity

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The minimum va for a mobile home lot

A

16000va

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Table - demand factors for mobile homes

A

550.31

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Areas where lighting are not considered continuous

A

Dwelling units

Motel rooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

For a service over 200a, these demand factors can be applied to the neutral

A

1st 200a at 100%

Remainder at 70%

Nonlinear loads at 100%

17
Q

For a 3 phase service, when converting from va or wattage to amps, a factor of ___ must be applied to the voltage

A

1.732

18
Q

For a multi-family dwelling with laundry on premises, the laundry circuit becomes the ___, and can be reduced by what demand factors

A

Houseload

None

19
Q

For a multi-family optional method calculation, the table for demand factors is

A

220.84

20
Q

For a multi-family optional method calculation, heat and a/c is calculated

A

100% of A/C

100% of Heat

21
Q

When calculating a duplex service size, the smaller of ___ shall be permitted

A

The standard method of the two dwelling units

The optional method per 220.84 of 3 identical units

22
Q

Per Art ___, the largest motor in HP shall have ___% added to the final demand load

A

220.50

25%