Calculations for Commercial Flashcards
Demand factors for non-dwelling recept. loads
220.44
1st 10kva at 100%
Remainder at 50%
In no case shall the feeder demand load for commercial cooking equipment be less than
The summation of the two largest cooking equipment’s nameplate
Recepts. for heavy duty lampholders will be considered ___va
600
Show window lighting will be calculated on the basis of ___va per ___ linear ft
200
1
Lighting/Receptacle demand factors of Table 220.42 can be applied to
Dwelling units, hotels/motels, hospitals, and storage warehouses
The NEC requires a sign circuit for commercial buildings that are accessible to pedestrians. Their rating shall be considered
20a, 1200va
For a multi-outlet assembly used with simultaneous appliances, it’s load shall be considered
180va per ft or fraction there of
The demand factors for recepts. in Table 220.44 are
1st 10kva at 100%
Remainder at 50%
The receptacle demand load for banks and offices is considered the larger of
The known number of recepts x 180va, 220.44
1va per sq ft
Motors, when calculated for a service, have their demand load multiplied by
125%
The sign ckt is considered a
continuous load
When the OCPD is rated over 800a, the wire must be sized to
match the rating of the OCPD
The smallest conductor that can be paralleled is
1/0
A neutral conductor must be sized no smaller than per Table
250.102(C)(1)
Transformers are sized by
100% of the continuous load and noncontinuous load