Calculations for Commercial Flashcards

1
Q

Demand factors for non-dwelling recept. loads

A

220.44

1st 10kva at 100%
Remainder at 50%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

In no case shall the feeder demand load for commercial cooking equipment be less than

A

The summation of the two largest cooking equipment’s nameplate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Recepts. for heavy duty lampholders will be considered ___va

A

600

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Show window lighting will be calculated on the basis of ___va per ___ linear ft

A

200

1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Lighting/Receptacle demand factors of Table 220.42 can be applied to

A

Dwelling units, hotels/motels, hospitals, and storage warehouses

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The NEC requires a sign circuit for commercial buildings that are accessible to pedestrians. Their rating shall be considered

A

20a, 1200va

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

For a multi-outlet assembly used with simultaneous appliances, it’s load shall be considered

A

180va per ft or fraction there of

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The demand factors for recepts. in Table 220.44 are

A

1st 10kva at 100%

Remainder at 50%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The receptacle demand load for banks and offices is considered the larger of

A

The known number of recepts x 180va, 220.44

1va per sq ft

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Motors, when calculated for a service, have their demand load multiplied by

A

125%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The sign ckt is considered a

A

continuous load

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When the OCPD is rated over 800a, the wire must be sized to

A

match the rating of the OCPD

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

The smallest conductor that can be paralleled is

A

1/0

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A neutral conductor must be sized no smaller than per Table

A

250.102(C)(1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Transformers are sized by

A

100% of the continuous load and noncontinuous load

How well did you know this?
1
Not at all
2
3
4
5
Perfectly