C-10 Trade 3 Flashcards
An example of inductive dielectric heating is a(n):
a. furnace
b. oven
c. microwave
d. heater
c. microwave
One million watts equal one:
a. kilowatt
b. milliwatt
c. nanowatt
d. megawatt
d. megawatt
Cal/OSHA requires guardrails for scaffolds over _____ in height.
a. 5’
b. 7-½’
c. 17’
d. 36’
b. 7-½’
The device used to measure large values of alternating current is a:
a. voltage transformer
b. wattmeter
c. current transformer
d. voltmeter
c. current transformer
For how much of the normal ampacity must branch circuit conductors supplying continuous loads be sized?
a. 80%
b. 100%
c. 125%
d. 150%
c. 125%
A 50 kVA transformer supplies 480 V and 40 A. What is its kW rating?
a. 19 kW
b. 40 kW
c. 68 kW
d. 77 kW
a. 19 kW
The allowable voltage drop of a branch circuit connected to a heater is:
a. 3%
b. 5%
c. 10%
d. 15%
a. 3%
A 75 kVA, three-phase transformer has 480 V, what is its amperage?
a. 90 amps
b. 60 amps
c. 30 amps
d. 25 amps
a. 90 amps
<em>75,000 / 480 = 156.25</em>
<em>156.25 / 1.73 = 90.31 amps</em>
The total resistance of three 12-ohm resistors wired in parallel is:
a. 4 ohms
b. 12 ohms
c. 25 ohms
d. 36 ohms
a. 4 ohms
<em>A parallel circuit is a circuit in which the resistors are arranged with their heads connected together, and their tails connected together. The current in a parallel circuit breaks up, with some flowing along each parallel branch and re-combining when the branches meet again. The voltage across each resistor in parallel is the same.</em>
<em>The total resistance of a set of resistors in parallel is found by adding up the reciprocals of the resistance values, and then taking the reciprocal of the total:</em>
<em>equivalent resistance of resistors in parallel: 1 / R = 1 / R1 + 1 / R2 + 1 / R3 +…</em>
Bending conduit is best done with a:
a. field hickey
b. fixture hickey
c. finial
d. pipe wrench
a. field hickey
For an electric appliance with a 17.5 A load, the overcurrent device must not exceed:
a. 15 amps
b. 20 amps
c. 25 amps
d. 30 amps
c. 25 amps
<em>17.5 * 125%=21.875 (25A next standard size larger)</em>
The general lighting load in dwellings is based upon ______ per square foot.
a. 3 watts
b. 5 watts
c. 10 watts
d. 15 watts
a. 3 watts
Where may you use nonmetallic-sheathed cable?
a. inside floors and walls
b. buried in cinder fill
c. direct burial
d. air conditioning duct
a. inside floors and walls
The demand factor of a fixed electric space heater is 65%. A central air-conditioning unit in the house has a demand factor of 100%. The air-conditioner also acts as a heat pump. What percent should be added to the heating circuit (i.e., space heater)?
a. 35%
b. 65%
c. 80%
d. 100%
d. 100%
What type of insulation is needed underground?
a. THW
b. XHHN
c. THN
d. THHN
a. THW
The current of a high-voltage supply line is best measured with a:
a. voltage transformer
b. clamp-on ammeter
c. current transformer
d. transformer insulated in mineral oil
b. clamp-on ammeter