C-10 Trade 2 Flashcards
When deciding where to locate an electric meter:
a. check with the owner
b. check with the building department
c. check with the utility company
d. check with the CSLB
c. check with the utility company
Why is a conduit bender the best tool for bending EMT?
a. it produces a perfect bend
b. it is easier to pull than a hickey
c. it keeps the interior volume of the pipe unchanged
d. it is most portable
c. it keeps the interior volume of the pipe unchanged
When troubleshooting a living room circuit, you observe that one light will not go on but another is brighter than normal. What might be the problem?
a. a short
b. an open hot wire
c. an open neutral
d. high ground resistance at panel
a. a short
If a fire detection sensor is to be wired to a control panel, it must be approved by:
a. the fire department
b. the manufacturer’s specifications
c. the authority having jurisdiction
d. the NEC
c. the authority having jurisdiction
What is not true of electrical equipment rated for hazardous locations?
a. arcs or sparks are contained within a rated housing
b. conduit seals limit an explosion to near the source
c. only cool gases are allowed to escape from an electrical explosion and into the hazardous location
d. an explosion will not occur inside rated equipment
d. an explosion will not occur inside rated equipment
What is the daily cost for a 600-watt appliance that runs 5 hours a day at $0.14 per kWh?
a. $0.48
b. $0.42
c. $0.70
d. $1.40
b. $0.42
A building has a 120/208 V wiring system and requires a 400-amp service. A 480 V power line is available. What size and type of transformer is needed?
a. 480 V, 400-amp, 1.73:1 delta-wye with 120 V center taps
b. 480 V, 100 amp in, 1:4 delta with neutral leg
c. 480 V, 100-amp in, wye-connected 4:1 step-down
d. 480/208 V, 400-amp in, 120 T-tap delta step-down
c. 480 V, 100-amp in, wye-connected 4:1 step-down
Exterior connectors used on conduit are:
a. waterproof
b. water-resistant
c. either water-resistant or waterproof
d. galvanized
c. either water-resistant or waterproof
What type of light can be mounted on the wall in a closet?
a. ceramic keyless
b. fluorescent
c. open incandescent
d. partly closed incandescent
b. fluorescent
The allowed wire fill in a nipple is usually:
a. 20%
b. 60%
c. 75%
d. 90%
b. 60%
If a lighting circuit has two three-way switches in the black line and you are asked to add another switch, into which circuit leg would you tap a four-way switch?
a. red
b. black
c. white
d. green
b. black
Where would you not use nonmetallic sheathed cable?
a. strip mall
b. two story apartment
c. house remodel
d. five story condo
d. five story condo
What is the maximum height for an office light switch?
a. 24”
b. 36”
c. 48”
d. 60”
c. 48”
One wall of a living room is 20’ long and finished entirely in glass panels. The specifications call for three receptacles along this wall. What should you do?
a. use floor receptacles
b. eliminate the receptacles
c. install two receptacles at the corners of adjacent walls and eliminate the third one
d. ask the contractor to get the specs changed
a. use floor receptacles
You have a three-phase motor with nine leads. How are the connections made?
a. phase I to 1,2,3; phase II to 4,5,6; phase III to 7,8,9
b. phase I to 1,7; phase II to 2,8; phase III to 3,9; wire 4,5,6 together
c. phase I to 1,2,3,4,5; phase II to 6,7; phase III to 8,9
d. phase I to 1,2,3,4,5; phase II to 6,7,8,9; phase III not connected
b. phase I to 1,7; phase II to 2,8; phase III to 3,9; wire 4,5,6 together
At an excavation, an Underground Service Alert (U.S.A.) marking on the dirt with red paint or chalk indicates:
a. gas lines
b. water lines
c. telephone lines
d. electric power lines
d. electric power lines

Which metal objects must be bonded when near a pool or spa?
a. ladders
b. light housings
c. base of diving board
d. all of the above
d. all of the above
You need to design a 120/208-volt system for small appliances, lights, etc. What type of transformers would you use?
a. delta - delta
b. wye - delta
c. delta - wye
d. wye - wye
d. wye - wye
Which parts in the following diagram can serve as part of the grounding electrode system?
a. 1, 3, 4, & 5
b. 4, 5, & 6
c. 2, 4, & 5
d. 1, 2, & 6

b. 4, 5, & 6
What is the maximum rating for a garbage disposal on a 20-amp branch circuit?
a. 50%
b. 70%
c. 80%
d. 90%
a. 50%
Where would a 208Y/120 V service most likely be installed?
a. single family residence
b. light industrial building
c. heavy industrial building
d. special purpose only
b. light industrial building
In which location is the use of a test meter with a CAT-II 600 volt safety rating strongly recommended?
a. low energy electronics in protected office equipment
b. outlets more than 10 meters (33 ft) from service panel
c. outlets 6 meters (20 ft) from service panel
d. main service panel
b. outlets more than 10 meters (33 ft) from service panel
Who schedules the next phase of work after the rough wiring is done?
a. city inspector
b. architect
c. owner
d. prime contractor
d. prime contractor
What is the minimum clearance above grade, as specified in the NEC, for a service drop up to 600 volts?
a. 8’
b. 10’
c. 12’
d. 15’
b. 10’
(A) Sheet Metal Auxiliary Gutters. The sum of the cross-sectional areas of all contained conductors at any cross section of a sheet metal an auxiliary gutter shall not exceed 20 percent of the interior cross-sectional area of the sheet metal auxiliary gutter. The adjustment factors in 310.15(B)(3)(a) shall be applied only where the number of current-carrying conductors, including neutral conductors classified as current-carrying under the provisions of 310.15(B)(5), exceeds 30. Conductors for signaling circuits
or controller conductors between a motor and its starter and used only for starting duty shall not be considered as current-carrying conductors.
(B) Nonmetallic Auxiliary Gutters. The sum of cross-sectional areas of all contained conductors at any cross section of the nonmetallic auxiliary gutter shall not exceed 20 percent of the interior cross-sectional area of the nonmetallic auxiliary gutter.
366.23 Ampacity of Conductors.
(A) Horizontal Support. Wireways shall be supported where run horizontally at each end and at intervals not to exceed 1.5 m (5 ft) or for individual lengths longer than 1.5 m (5 ft) at each end or joint, unless listed for other support intervals. The distance between supports shall not exceed 3 m (10 ft).
(B) Vertical Support. Vertical runs of wireways shall be securely supported at intervals not exceeding 4.5 m (15 ft) and shall not have more than one joint between supports. Adjoining wireway sections shall be securely fastened together to provide a rigid joint.

"Where conduit or tubing nipples having a maximum length not to exceed 24 in. are installed between boxes, cabinets, and similar enclosures, the nipples shall be permitted to be filled to 60 percent of their total cross-sectional area, and 310.15(B)(3)(a) adjustment factors need not apply to this condition."



Subsection (A)(2) states, "The total rating of utilization equipment fastened in place, other than luminaires (lighting fixtures), shall not exceed 50 percent of the branch-circuit ampere rating where lighting units, cord-and-plug-connected utilization equipment not fastened in place, or both, are also supplied."