Backflow / Cross Connection Flashcards
An approved assembly consisting of spring loaded check valves and air inlet valve installed between two resilient seated shutoff valves is:
PVB (pressure vacuum breaker)
An assembly consisting of two spring loaded check valves separated by a differential pressure relief valve is:
A reduced pressure backflow assembly
This backflow assembly consists of two internally loaded check valves (either spring or weight loaded)
DCVA
This assembly consists of an air inlet valve and a spring loaded check valve
PVBA
The relief valve of a RPBA maintains a differential pressure of at least
2 psig
This backflow assembly may also detect water loss or theft on a low hazard service
DCDA (double check detector assembly)
This backflow preventer must not be installed upstream of a shutoff valve
AVB
The air inlet valve of a PVBA must open at or above ___ psig
1
An RPBA installed more than ____ feet above the floor shall have a platform provided for servicing and testing.
5 ft (1500 mm)
Backflow preventer on a water service to protect the purveyor water supply but not the building occupants, referred to as ____ isolation
Premise isolation
The #1 check valve on a RPBA is spring loaded to the ____ position
Closed
The zone of reduced pressure in a RPBA will not be closer than ____ of the ____ pressure
2 psid (13.8 kPa) of the inlet pressure
The relief valve on a RPBA is held closed by
Supply line pressure
The check valves of a DCVA must hold in the direction of flow against
1 psig, equivalent of 27.7” of water column
Any backflow assembly installed in a piping system where debris is a problem should have a ____ installed upstream
Strainer