Assemblies Flashcards
Learn the four different backflow prevention assemblies
Which assembly has only one test cock?
SVB
Which assembly has four shut offs, four checks & 8 test cocks?
DCDA
Maximum allowable pressure loss across a Double check assembly?
10 PSIG
It is recommended that a DC be installed with its critical level a minimum of ____ inches above the floor?
12inches
What is the minimum pressure drop across each check of a DC in a static condition?
1.0 PSID
Where is the #2 test cock of a DC located?
upstream of check valve #1
What is considered to be critical level of a PVB if it is not marked?
The bottom of the valve body
What can be done if the air inlet valve of a PVB will not seat?
Increase the supply pressure
What is the reason for the meter on a DCDA ?
To detect unauthorized water usage
A DC may be used for what type of hazard only?
Low
The purpose of the bypass flow indicator is to detect low flow rates up to how many GPM ?
2GPM
The PVB shut-off valves are located where on the assembly?
At the inlet and outlet of the assembly
A DC consists of how many valves & checks?
2 of each
Are the checks of a DC interchangeable?
YES
Where is the #1 test cock located on a PVB?
Upstream of the check
Can the PVB & SVB be subjected to continuous pressure?
YES
What is the critical level of a PVB or SVB?
12 inches above the highest downstream use.
How many test cocks does a PVB have on the assembly?
2 test cocks
How many test cocks does an SVB have on the assembly?
One test cock
An SVB ‘s check must be drip-tight at ?
1.0 PSID