API 650 PRACTICE QUESTIONS Flashcards
API 650 covers material, design, fabrication, erection, and testing requirements for aboveground welded steel storage tanks. Internal pressure allowed for these tanks approximates atmospheric pressure. However, the internal pressures must not:
exceed the weight of the roof plates
1.1.1
Tanks that have bottoms that are not uniformly supported are:
not covered by API 650
1.1.1
Tanks covered by API 650 are restricted to a maximum operating temperature of ___degrees F, unless additional requirements of Appendix M of API 650 are followed.
200
1.1.1
who decides whether tanks constructed to API 650 will have SI dimensions and comply with applicable SI unit standards or have US Customary dimensions and comply with applicable US customary unit standards?
It shall be decided by a mutual agreement between the manufacturer and the purchaser.
1.1.3
Appendix A provides alternative simplified design requirements for tanks where the stressed components, such as shell plates and reinforcing plates, are limited to a maximum nominal thickness of_____, including corrosion allowance.
13mm (1/2in)
A1.1
Who is responsible for complying with all of the provisions of API 650 when a new tank is built?
The manufacturer
1.3
The term used to define the condition where-as the mid-thickness centerlines of shell plates in all shell courses coincide is____________.
Centerline-stacked
3.1
Required sections of this Standard become _______ if the Standard has been adopted by a legs jurisdiction.
Mandatory
3.1.5
The lowest temperature considered in the design shall be assumed to be _______ above the lowest one-day mean ambient temperature of the locality where the tank is to be installed.
15 degrees F
3.6
Material used to construct a tank shall conform to the specifications of API 650; however, other material may be used:
provided that the material is certified to meet all requirements of a material listed in API 650 and the purchaser approves.
When any new or unused plate and pipe material cannot be completely identified by records that are satisfactory, the material may be used in the construction of tanks covered by API 650 only if the:
material passes tests prescribed in Appendix N of API 650
4.1.3
Whether an edge-thickness or weight basis is used in the ordering of plate for construction of tanks, an under run not more than _____ inch from the computed design thickness or the minimum permitted thickness is acceptable
- 01
4. 2.1.2.3
Shell plates for API 650 tanks are limited tow hat maximum thickness?
- 75 inches
4. 2.1.4
Plates thicker than_____ inches shall be normalized or quench tempered, killed, made to fine-grain practice, and impact tested.
- 50
4. 2.1.4
A purchaser requires a tank to be built from ASTM A-283 Grade C plate. What maximum thickness limitation is placed on this plate?
- 00 inch
4. 2.2c
Define a full-fillet weld
A full-fillet weld is a fillet weld whose sizes is equal to the thickness of the thinner joined member.
5.1.1.7